Insulation jacket
1
Helix of copper tape or copper wire
2
Copper wire shield
3
Inner insulation
4
Cable core
5
Selecting the control cables
■
Shielding
Only use shielded control cables.
Use a double-shielded twisted pair cable for analog signals. This type of cable is
recommended for the pulse encoder signals also. Use one individually shielded pair for
each signal. Do not use common return for different analog signals.
A double-shielded cable (a) is the best alternative for low-voltage digital signals, but
single-shielded (b) twisted pair cable is also acceptable.
a
b
■
Signals in separate cables
Run analog and digital signals in separate, shielded cables. Do not mix 24 V DC and
115/230 V AC signals in the same cable.
■
Signals that can be run in the same cable
If their voltage does not exceed 48 V, relay-controlled signals can be run in the same cables
as digital input signals. The relay-controlled signals should be run as twisted pairs.
■
Relay cable
The cable type with braided metallic shield (for example ÖLFLEX by LAPPKABEL, Germany)
has been tested and approved by ABB.
■
Control panel to drive cable
Use EIA-485 with male RJ-45 connector, cable type Cat 5e or better. The maximum permitted
length of the cable is 100 m (328 ft).
72 Guidelines for planning the electrical installation
Содержание ACS880-04FXT
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 04FXT drive module packages Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 40: ...40 ...
Страница 54: ...54 ...
Страница 82: ...82 ...
Страница 86: ...M10 86 Electrical installation ...
Страница 106: ...106 ...
Страница 114: ...FSO xx safety functions module connection X12 See the user manual of the FSO xx module 114 Control unit of the drive ...
Страница 118: ...118 ...
Страница 122: ...122 ...
Страница 132: ...132 ...
Страница 136: ...136 ...
Страница 158: ...158 ...
Страница 160: ...Standard configuration IP00 UL Type Open 160 Dimension drawings ...
Страница 161: ...Drive module with optional support brackets IP00 UL Type Open Dimension drawings 161 ...
Страница 162: ...Drive module with optional full size input and output power cable terminals and IP20 shrouds 162 Dimension drawings ...
Страница 163: ...Mounting plate opening 3AXD50000038119 Dimension drawings 163 ...
Страница 164: ...3AXD50000038119 164 Dimension drawings ...
Страница 182: ... Declaration of conformity 182 The Safe torque off function ...
Страница 183: ...The Safe torque off function 183 ...
Страница 184: ...184 ...