2×300
2×300
0960A-7
2×300
2×300
1080A-7
2×400
2×300
1320A-7
The cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire insulation at 40 °C
(104 °F) ambient temperature. Not more than three current-carrying conductors in raceway or cable or earth
(directly buried). For other conditions, dimension the cables according to local safety regulations, appropriate
input voltage and the load current of the drive.
1)
The table gives DC cable types when the cables are outside the cabinet. For DC cables inside the cabinet,
select a cable capable of carrying 2/3 of the continuous output current of one drive module.
*)
Connection (1× xxx): One phase conductor of the three-phase cable between the DC+ terminals of the drive
modules and another phase conductor of the three-phase cable between the DC- terminals of the drive
modules. The third phase conductor unconnected.
**)
Connection (2 × (3 × xxx)): two phase conductors of one three-phase cable between the DC+ terminals of
the drive modules and two phase conductors of the second three-phase cable between the DC- terminals
of the drive modules. The third phase conductors unconnected.
Terminal and entry data for the power cables
The maximum accepted cable size is 4×(3×240) mm
2
or 4×(3×500 AWG). Screw size for
connecting busbars to the drive module input and output busbars: M12, tightening torque
50…75 N·m.
■
Units without full-size output cable connection terminals and with a
common mode filter (+E208)
It is possible to use the maximum cable size (4×[3×240] mm
2
or 4 ×[(3×500 AWG]) only
with special cable lugs and additional insulation. For more information, contact your local
ABB representative.
Terminal data for the control cables
See section
Default I/O connection diagram (page 110)
Electrical power network specification
ACS880-04FXT-xxxx-3 drives: 380…415 VAC 3-phase +10%…-15%. This is in-
dicated in the type designation label as typical input voltage level 3~400 V AC.
Voltage (U
1
)
ACS880-04FXT-xxxx-5 drives: 380…500 V AC 3-phase +10%…-15%. This is in-
dicated in the type designation label as typical input voltage levels
3~400/480/500 V AC.
ACS880-04FXT-xxxx-7 drives: 525…690 V AC 3-phase +10%…-15%. This is in-
dicated in the type designation label as typical input voltage levels 3~525/600/690 V
AC.
TN (grounded) and IT (ungrounded) systems
Network type
Maximum allowable prospective short-circuit current is 65 kA when protected by
the fuses given in the fuse table.
Short-circuit withstand
strength (IEC 61439-1)
The drive is suitable for use on a circuit capable of delivering not more than
100,000 rms symmetrical amperes at 600 V maximum when protected by the fuses
given in the fuse table.
Short-circuit current
protection (UL 508A)
Technical data 149
Содержание ACS880-04FXT
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 04FXT drive module packages Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 40: ...40 ...
Страница 54: ...54 ...
Страница 82: ...82 ...
Страница 86: ...M10 86 Electrical installation ...
Страница 106: ...106 ...
Страница 114: ...FSO xx safety functions module connection X12 See the user manual of the FSO xx module 114 Control unit of the drive ...
Страница 118: ...118 ...
Страница 122: ...122 ...
Страница 132: ...132 ...
Страница 136: ...136 ...
Страница 158: ...158 ...
Страница 160: ...Standard configuration IP00 UL Type Open 160 Dimension drawings ...
Страница 161: ...Drive module with optional support brackets IP00 UL Type Open Dimension drawings 161 ...
Страница 162: ...Drive module with optional full size input and output power cable terminals and IP20 shrouds 162 Dimension drawings ...
Страница 163: ...Mounting plate opening 3AXD50000038119 Dimension drawings 163 ...
Страница 164: ...3AXD50000038119 164 Dimension drawings ...
Страница 182: ... Declaration of conformity 182 The Safe torque off function ...
Страница 183: ...The Safe torque off function 183 ...
Страница 184: ...184 ...