ACS850-04 Fuse
Type A
03A0-5, 03A6-5, 04A8-5, 06A0-5, 08A0-5
16
010A-5 20
014A-5, 018A-5
32
025A-5, 030A-5
63
035A-5, 044A-5, 050A-5
100
061A-5, 078A-5, 094A-5, 103A-5
160
144A-5, 166A-5
315
202A-5, 225A-5
400
260A-5 500
290A-5 550
430A-5 800
521A-5 1000
602A-5 1250
693A-5, 720A-5
1600
EMC
The compliance of the drive modules with the EMC directive is specified in the relevant
hardware manual for the single drive configuration. Notice that different common DC
configurations have not been tested from the EMC point of view. However, the
available mains filters can be used in the AC supply of the common DC system, but the
rules to meet the different EMC categories are not available.
Installation
See the relevant hardware manual for the installation (mechanical and electrical)
guidelines of the drive modules and external options.
Supply
Use the same supply connection point. All converters must be fed from the same
transformer. The supply impedance is an important parameter, which influences the
current distribution. All converters must have equal supply impedance.
Phase loss guard
It is recommended to use phase loss guard in the input supplies of all of the
converters. If phase loss guard is not used and the fuse of one of the input supply
phases blows, the semiconductors of the converters may be overloaded and damaged.
Common DC configurations