Planning the electrical installation
60
A double-shielded cable is the best alternative for low-voltage digital signals but
single-shielded twisted pair cable is also usable.
Signals in separate cables
Run analog and digital signals in separate, shielded cables.
Never mix 24 V DC and 115/230 V AC signals in the same cable.
Signals allowed to be run in the same cable
Relay-controlled signals, providing their voltage does not exceed 48 V, can be run in
the same cables as digital input signals. It is recommended that the relay-controlled
signals be run as twisted pairs.
Relay cable type
The cable type with braided metallic screen (for example ÖLFLEX by LAPPKABEL,
Germany) has been tested and approved by ABB.
Control panel cable length and type
In remote use, the cable connecting the control panel to the drive must not exceed 3
meters (10 ft). The cable type tested and approved by ABB is used in control panel
option kits.
Routing the cables
Route the motor cable away from other cable routes. Motor cables of several drives
can be run in parallel installed next to each other. It is recommended that the motor
cable, input power cable and control cables be installed on separate trays. Avoid
long parallel runs of motor cables with other cables in order to decrease
electromagnetic interference caused by the rapid changes in the drive output
voltage.
Where control cables must cross power cables ensure that they are arranged at an
angle as near to 90 degrees as possible. Do not run extra cables through the drive.
The cable trays must have good electrical bonding to each other and to the
grounding electrodes. Aluminium tray systems can be used to improve local
equalizing of potential.
Double-shielded twisted pair
cable
Single-shielded twisted pair
cable
Содержание ACS850-04 series
Страница 1: ...ABB machinery drives Hardware manual ACS850 04 drive modules 160 to 560 kW 200 to 700 hp ...
Страница 4: ......
Страница 12: ...Table of contents 12 ...
Страница 20: ...Safety instructions 20 ...
Страница 26: ...Introduction to the manual 26 ...
Страница 81: ...Installation 81 Assembly drawing frame G1 3AUA0000132078 ...
Страница 82: ...Installation 82 Assembly drawing frame G2 3AUA0000132062 ...
Страница 83: ...Installation 83 Assembly drawing air baffles 3AUA0000132062 ...
Страница 92: ...Installation 92 3 6a 6b 5 4 8 4 8 6a 6b 7a 7b 7b ...
Страница 93: ...Installation 93 Assembly drawing of installing the drive module to the cabinet frame G1 3AUA0000132078 ...
Страница 94: ...Installation 94 Assembly drawing of installing the drive module to the cabinet frame G2 3AUA0000132062 ...
Страница 98: ...Installation 98 3AUA0000038989 TXD transmitter RXD receiver JRIB V2 V1 V7 V6 1 2 APOW JINT 2 JRIB 1 4 3 JGDR ...
Страница 112: ...Installation checklist 112 ...
Страница 114: ...Start up 114 ...
Страница 116: ...Fault tracing 116 ...
Страница 140: ...Technical data 140 ...
Страница 142: ...Dimension drawings 142 Frame G1 Drive module dimensions ...
Страница 143: ...Dimension drawings 143 Frame G1 Drive module dimensions with optional cabling panels H381 ...
Страница 144: ...Dimension drawings 144 ...
Страница 145: ...Dimension drawings 145 Frame G1 Cabling panels H383 installed into a Rittal TS 8 cabinet ...
Страница 146: ...Dimension drawings 146 Frame G2 Drive module dimensions ...
Страница 147: ...Dimension drawings 147 Frame G2 Drive module dimensions with optional cabling panels H381 ...
Страница 148: ...Dimension drawings 148 ...
Страница 149: ...Dimension drawings 149 Frame G2 Cabling panels H383 installed into a Rittal TS 8 cabinet ...
Страница 150: ...Dimension drawings 150 Frames G1 and G2 Bottom plate 3AUA0000082240 ...
Страница 151: ...Dimension drawings 151 Frames G1 and G2 Air baffles 3AUA0000138986 ...
Страница 152: ...Dimension drawings 152 ...
Страница 162: ...du dt filters 162 ...
Страница 164: ...3AUA0000081249 Rev C EN 2013 04 11 Contact us www abb com drives www abb com drivespartners ...