Planning the electrical installation
56
Selecting the power cables
General rules
Dimension the input power and motor cables
according to local regulations
:
• Dimension the cable to carry the drive load current. See chapter
for the rated currents.
• Select a cable rated for at least 70
°
C (158
°
F) maximum permissible temperature
of conductor in continuous use. For US, see
page
• The inductance and impedance of the PE conductor/cable (grounding wire) must
be rated according to permissible touch voltage appearing under fault conditions
(so that the fault point voltage will not rise excessively when a ground fault
occurs).
• 600 V AC cable is accepted for up to 500 V AC.
Use symmetrical shielded motor cable, see page
.
Note:
When continuous metal conduit is employed, shielded cable is not required.
The conduit must have bonding at both ends as with cable shield.
A four-conductor system is allowed for input cabling, but shielded symmetrical cable
is recommended. To operate as a protective conductor, the shield conductivity
requirements according to IEC 60439-1 are shown below when the protective
conductor is made of the same metal as the phase conductors:
Compared to a four-conductor system, the use of symmetrical shielded cable
reduces electromagnetic emission of the whole drive system as well as the stress on
motor insulation, bearing currents and wear.
Keep the motor cable and its PE pigtail (twisted shield) as short as possible to
reduce high-frequency electromagnetic emissions.
Cross-sectional area of the phase
conductors
S (mm
2
)
Minimum cross-sectional area of the
corresponding protective conductor
S
p
(mm
2
)
S < 16
S
16 < S < 35
16
35 < S
S/2
Содержание ACS850-04 series
Страница 1: ...ABB machinery drives Hardware manual ACS850 04 drive modules 160 to 560 kW 200 to 700 hp ...
Страница 4: ......
Страница 12: ...Table of contents 12 ...
Страница 20: ...Safety instructions 20 ...
Страница 26: ...Introduction to the manual 26 ...
Страница 81: ...Installation 81 Assembly drawing frame G1 3AUA0000132078 ...
Страница 82: ...Installation 82 Assembly drawing frame G2 3AUA0000132062 ...
Страница 83: ...Installation 83 Assembly drawing air baffles 3AUA0000132062 ...
Страница 92: ...Installation 92 3 6a 6b 5 4 8 4 8 6a 6b 7a 7b 7b ...
Страница 93: ...Installation 93 Assembly drawing of installing the drive module to the cabinet frame G1 3AUA0000132078 ...
Страница 94: ...Installation 94 Assembly drawing of installing the drive module to the cabinet frame G2 3AUA0000132062 ...
Страница 98: ...Installation 98 3AUA0000038989 TXD transmitter RXD receiver JRIB V2 V1 V7 V6 1 2 APOW JINT 2 JRIB 1 4 3 JGDR ...
Страница 112: ...Installation checklist 112 ...
Страница 114: ...Start up 114 ...
Страница 116: ...Fault tracing 116 ...
Страница 140: ...Technical data 140 ...
Страница 142: ...Dimension drawings 142 Frame G1 Drive module dimensions ...
Страница 143: ...Dimension drawings 143 Frame G1 Drive module dimensions with optional cabling panels H381 ...
Страница 144: ...Dimension drawings 144 ...
Страница 145: ...Dimension drawings 145 Frame G1 Cabling panels H383 installed into a Rittal TS 8 cabinet ...
Страница 146: ...Dimension drawings 146 Frame G2 Drive module dimensions ...
Страница 147: ...Dimension drawings 147 Frame G2 Drive module dimensions with optional cabling panels H381 ...
Страница 148: ...Dimension drawings 148 ...
Страница 149: ...Dimension drawings 149 Frame G2 Cabling panels H383 installed into a Rittal TS 8 cabinet ...
Страница 150: ...Dimension drawings 150 Frames G1 and G2 Bottom plate 3AUA0000082240 ...
Страница 151: ...Dimension drawings 151 Frames G1 and G2 Air baffles 3AUA0000138986 ...
Страница 152: ...Dimension drawings 152 ...
Страница 162: ...du dt filters 162 ...
Страница 164: ...3AUA0000081249 Rev C EN 2013 04 11 Contact us www abb com drives www abb com drivespartners ...