Planning the electrical installation
33
Restarting after an emergency stop
After an emergency stop, the emergency stop button must be released and the drive
started by turning the operating switch of the drive from position “ON” to “START”.
Prevention of Unexpected Start (ACS800-07/U7 only)
The drive can be equipped with an optional Prevention of Unexpected Start function
according to standards IEC/EN 60204-1: 1997; ISO/DIS 14118: 2000 and EN 1037:
1996.
The Prevention of Unexpected Start function disables the control voltage of the
power semiconductors, thus preventing the inverter from generating the AC voltage
required to rotate the motor. By using this function, short-time operations (like
cleaning) and/or maintenance work on non-electrical parts of the machinery can be
performed without switching off the AC power supply to the drive.
The operator activates the Prevention of Unexpected Start function by opening a
switch on a control desk. An indicating lamp on the control desk will light, signalling
that the prevention is active. The switch can be locked out.
The user must install on a control desk near the machinery:
• switching/disconnecting device for the circuitry. “Means shall be provided to
prevent inadvertent, and/or mistaken closure of the disconnecting device.”
EN 60204-1: 1997.
• indicating lamp; on = starting the drive is prevented, off = drive is operative.
For connections to the drive, see the circuit diagram delivered with the drive.
WARNING!
The Prevention of Unexpected Start function does not disconnect the
voltage of the main and auxiliary circuits from the drive. Therefore maintenance work
on electrical parts of the drive or the motor can only be carried out after isolating the
drive system from the main supply.
Note:
When a running drive is stopped by using the Prevention of Unexpected Start
function, the drive will stop by coasting. If this is not acceptable (e.g. causes danger),
the drive and machinery must be stopped using the appropriate stopping mode
before using this function.
Содержание ACS800-02
Страница 1: ...ACS800 Hardware Manual ACS800 02 Drives 45 to 500 kW ACS800 U2 Drives 60 to 600 HP ...
Страница 4: ......
Страница 10: ...Safety instructions 10 ...
Страница 20: ...About this manual 20 ...
Страница 26: ...The ACS800 02 U2 26 ...
Страница 42: ...Planning the electrical installation 42 ...
Страница 76: ...Installation checklist 76 ...
Страница 106: ...Technical data 106 ...
Страница 107: ...Dimensional drawings 107 Dimensional drawings The dimensions are given in milllimetres and inches ...
Страница 108: ...Dimensional drawings 108 Frame size R7 US gland conduit plate 64579746 H ...
Страница 109: ...Dimensional drawings 109 Frame size R8 3AFE 64564161 D US gland conduit plate ...
Страница 110: ...Dimensional drawings 110 Frame size R7 with enclosure extension bottom entry 64625942 1 2 B ...
Страница 111: ...Dimensional drawings 111 64625942 2 2 C ...
Страница 112: ...Dimensional drawings 112 Frame size R7 with enclosure extension top entry 64626264 1 2 C ...
Страница 113: ...Dimensional drawings 113 64626264 2 2 C ...
Страница 114: ...Dimensional drawings 114 Frame size R8 with enclosure extension bottom entry 3AFE 64626388 1 2 B ...
Страница 115: ...Dimensional drawings 115 3AFE 64626388 2 2 B ...
Страница 116: ...Dimensional drawings 116 Frame size R8 with enclosure extension top entry 3AFE 64626370 1 2 C ...
Страница 117: ...Dimensional drawings 117 3AFE 64626370 2 2 C ...
Страница 118: ...Dimensional drawings 118 ...
Страница 127: ......