Planning the electrical installation
28
To avoid damage to motor bearings, insulated N-end (non-driven end) bearings and
output filters from ABB must be used according to the following table. In addition, the
cables must be selected and installed according to the instructions given in this
manual. Three types of filters are used individually or in combinations:
• optional du/dt filter (protects motor insulation system and reduces bearing
currents).
• common mode filter (mainly reduces bearing currents)
• light common mode filter (mainly reduces bearing currents).
The common mode filter is composed of toroidal cores installed inside the drive at
the factory.
Requirements table
The following table shows how to select the motor insulation system and when optional ABB du/dt filter,
insulated N-end (non-driven end) motor bearings and ABB common mode filters
are required. The
motor manufacturer should be consulted regarding the construction of the motor insulation and
additional requirements for explosion-safe (EX) motors. Failure of the motor to fulfil the following
requirements or improper installation may shorten motor life or damage the motor bearings.
M
a
nuf
a
c
tur
e
r
Motor type
Nominal mains
voltage (AC line
voltage)
Requirement for
Motor insulation
system
ABB du/dt filter, insulated N-end bearing and ABB common mode
filter
P
N
< 100 kW
and
frame size < IEC 315
100 kW <
P
N
< 350 kW
or
frame size > IEC 315
P
N
> 350 kW
or
frame size > IEC 400
P
N
< 134 HP
and frame size <
NEMA 500
134 HP <
P
N
< 469 HP
or frame size >
NEMA 500
P
N
> 469 HP
A
B
B
Random-
wound M2_
and M3_
U
N
< 500 V
Standard
-
+ N
+ N + CMF
500 V <
U
N
< 600 V Standard
+ du/dt
+ du/dt + N
+ du/dt + N + LCMF
or
Reinforced
-
+ N
+ N + CMF
600 V <
U
N
< 690 V Reinforced
+ du/dt
+ du/dt + N
+ du/dt + N + LCMF
Form-wound
HXR and AM_
380 V <
U
N
< 690 V Standard
n.a.
+ N + CMF
+ N + CMF
Old* form-
wound HX_
and modular
380 V <
U
N
< 690 V Check with the
motor
manufacturer.
+ du/dt with voltages over 500 V + N + CMF
Random-
wound HXR
and AM_
380 V <
U
N
< 690 V Check with the
motor
manufacturer.
+ du/dt with voltages over 500 V + N + CMF
Содержание ACS800-02
Страница 1: ...ACS800 Hardware Manual ACS800 02 Drives 45 to 500 kW ACS800 U2 Drives 60 to 600 HP ...
Страница 4: ......
Страница 10: ...Safety instructions 10 ...
Страница 20: ...About this manual 20 ...
Страница 26: ...The ACS800 02 U2 26 ...
Страница 42: ...Planning the electrical installation 42 ...
Страница 76: ...Installation checklist 76 ...
Страница 106: ...Technical data 106 ...
Страница 107: ...Dimensional drawings 107 Dimensional drawings The dimensions are given in milllimetres and inches ...
Страница 108: ...Dimensional drawings 108 Frame size R7 US gland conduit plate 64579746 H ...
Страница 109: ...Dimensional drawings 109 Frame size R8 3AFE 64564161 D US gland conduit plate ...
Страница 110: ...Dimensional drawings 110 Frame size R7 with enclosure extension bottom entry 64625942 1 2 B ...
Страница 111: ...Dimensional drawings 111 64625942 2 2 C ...
Страница 112: ...Dimensional drawings 112 Frame size R7 with enclosure extension top entry 64626264 1 2 C ...
Страница 113: ...Dimensional drawings 113 64626264 2 2 C ...
Страница 114: ...Dimensional drawings 114 Frame size R8 with enclosure extension bottom entry 3AFE 64626388 1 2 B ...
Страница 115: ...Dimensional drawings 115 3AFE 64626388 2 2 B ...
Страница 116: ...Dimensional drawings 116 Frame size R8 with enclosure extension top entry 3AFE 64626370 1 2 C ...
Страница 117: ...Dimensional drawings 117 3AFE 64626370 2 2 C ...
Страница 118: ...Dimensional drawings 118 ...
Страница 127: ......