IT (ungrounded) systems
A drive equipped with no EMC filter or with EMC E210 is suitable for IT
(ungrounded systems). If the drive is equipped with EMC E202, disconnect
the filter before connecting the drive to an ungrounded system. For detailed
instructions on how to do this, please contact your local ABB representative.
WARNING!
If a drive with EMC E202 is installed on an IT system [an
ungrounded power system or a high resistance-grounded (over 30 ohms) power
system], the system will be connected to earth potential through the EMC filter
capacitors of the drive. This may cause danger or damage the unit.
Required tools
• set of screw drivers
• torque wrench with 500 mm (20 in.) or 2 x 250 mm (2 x 10 in.) extension bar
• 19 mm (3/4 in.) socket
for frame size R7: 13 mm (1/2 in.) magnetic end socket
for frame size R8: 17 mm (11/16 in.) magnetic end socket.
Checking the insulation of the assembly
Every drive has been tested for insulation between the main circuit and the chassis
(2500 V rms 50 Hz for 1 second) at the factory. Therefore, do not make any voltage
tolerance or insulation resistance tests (e.g. hi-pot or megger) on any part of the
drive. Check the insulation of the assembly as follows.
WARNING!
Check the insulation before connecting the drive to the mains. Make
sure that the drive is disconnected from the mains (input power).
1. Check that the motor cable is disconnected from the drive output terminals U2,
V2 and W2.
2. Measure the insulation resistances of the motor cable and the motor between
each phase and the Protective Earth by using a measuring voltage of 1 kV DC.
The insulation resistance must be higher than 1 Mohm.
PE
ohm
M
Содержание ACS800-02
Страница 1: ...ACS800 Hardware Manual ACS800 02 Drives 45 to 500 kW ACS800 U2 Drives 60 to 600 HP ...
Страница 4: ......
Страница 10: ...Safety instructions 10 ...
Страница 20: ...About this manual 20 ...
Страница 26: ...The ACS800 02 U2 26 ...
Страница 42: ...Planning the electrical installation 42 ...
Страница 76: ...Installation checklist 76 ...
Страница 106: ...Technical data 106 ...
Страница 107: ...Dimensional drawings 107 Dimensional drawings The dimensions are given in milllimetres and inches ...
Страница 108: ...Dimensional drawings 108 Frame size R7 US gland conduit plate 64579746 H ...
Страница 109: ...Dimensional drawings 109 Frame size R8 3AFE 64564161 D US gland conduit plate ...
Страница 110: ...Dimensional drawings 110 Frame size R7 with enclosure extension bottom entry 64625942 1 2 B ...
Страница 111: ...Dimensional drawings 111 64625942 2 2 C ...
Страница 112: ...Dimensional drawings 112 Frame size R7 with enclosure extension top entry 64626264 1 2 C ...
Страница 113: ...Dimensional drawings 113 64626264 2 2 C ...
Страница 114: ...Dimensional drawings 114 Frame size R8 with enclosure extension bottom entry 3AFE 64626388 1 2 B ...
Страница 115: ...Dimensional drawings 115 3AFE 64626388 2 2 B ...
Страница 116: ...Dimensional drawings 116 Frame size R8 with enclosure extension top entry 3AFE 64626370 1 2 C ...
Страница 117: ...Dimensional drawings 117 3AFE 64626370 2 2 C ...
Страница 118: ...Dimensional drawings 118 ...
Страница 127: ......