322 Parameters
All stop
Autochange is done when all the motors are stopped.
The PID sleep feature (parameters
) must be used for the drive to stop
when the process demand is low.
12
Even wear
The running time of the motors are balanced by the drive.
When the difference in running time between the motors with
the least and most running hours exceeds the time defined by
parameter
, the autochange
occurs.
The running hours of the motors can be found in group
PFC maintenance and monitoring
13
Source selection (see
on page
). -
Specifies the interval that is used in setting
of
parameter
.
1.00 h
0.00…42949672.95
h
Time.
1 = 1 h
Specifies the maximum wear imbalance, or difference in
running times between any motor, used by the
setting of parameter
10.00 h
0.00…1000000.00
h
Time.
1 = 1 h
Upper speed limit for the Autochange to occur. The
Autochange occurs when:
• the condition defined in
is fulfilled and,
• the speed of the drive motor
is below
the speed limit defined in this parameter.
Note:
When the value is selected as 0%, this speed limit
check is disabled.
100.0%
0.0…300.0%
Speed/frequency in percentage of the nominal speed or
frequency of the drive motor.
1 = 1%
Selects whether only auxiliary motors or all motors are
included in the Autochange function.
All motors
All motors, including the one connected to the drive
participates in the autochange. The Autochange logic will
connect the drive to each of the motors according to setting of
parameter
e.
Note:
The first motor (PFC1) also requires the appropriate
hardware contactor connections and PFC1 must be defined
in one of the relay output source parameters.
0
Aux motors only
Only auxiliary (direct-on-line) motors are affected by the
autochange function.
Note:
PFC1 refers to the motor that is fixed to the drive and
must not be selected in any of the relay output source
parameters. Only the starting order of the auxiliary motors will
be rotated.
1
Defines if the PFC motor 1 can be started. An interlocked
PFC motor cannot be started.
0 = Interlocked (not available), 1 = Available.
Available.
PFC motor is
available
Interlocked. PFC
motor is not in use
PFC motor is interlocked and not available.
0
Available. PFC
motor is available
PFC motor is available.
1
No.
Name/Value
Description
Def/FbEq16
ACS580 FW.book Page 322 Wednesday, September 21, 2016 9:48 PM
Содержание ACS580 Series
Страница 88: ...84 ACS580 FW book Page 84 Wednesday September 21 2016 9 48 PM ...
Страница 146: ...142 Program features ACS580 FW book Page 142 Wednesday September 21 2016 9 48 PM ...
Страница 444: ...440 Fieldbus control through a fieldbus adapter ACS580 FW book Page 440 Wednesday September 21 2016 9 48 PM ...
Страница 461: ...ACS580 FW book Page 457 Wednesday September 21 2016 9 48 PM ...
Страница 462: ...3AXD0000016097 Rev D EN 2016 09 02 ACS580 FW book Page 458 Wednesday September 21 2016 9 48 PM ...