Parameters 321
Defines the acceleration time for the drive motor speed
compensation, when an auxiliary motor is stopped. This ramp
time is also used for the drive motor to accelerate after an
autochange has occurred.
The parameter sets the ramp-up time as seconds from zero
to maximum frequency (not from the previous reference to
the new reference).
1.00 s
0.00…1800.00 s
Time.
1 = 1 s
Defines the deceleration time for the drive motor speed
compensation, when an auxiliary motor is started. This ramp
time is also used for the drive motor to decelerate after an
autochange has occurred.
The parameter sets the ramp-up time as seconds from
maximum to zero frequency (not from the previous reference
to the new reference).
1.00 s
0.00…1800.00 s
Time.
1 = 1 s
Defines the way the autochange is triggered.
In all cases except
, the start order is moved one
step forward each time the autochange occurs. If the start
order initially is 1-2-3-4, after the first autochange the order
will be 2-3-4-1, etc.
For
, the start order will be determined so that the
running times of all motors remain within the defined limit.
Note:
Autochange only occurs when the speed of the drive is
below the speed defined by parameter
See also section
on page
Not selected
Autochange disabled.
0
Selected
Rising edge starts the autochange if autochange conditions
are met.
1
DI1
Autochange triggered by the rising edge of digital input DI1
(
, bit 0).
2
DI2
Autochange triggered by the rising edge of digital input DI2
(
, bit 1).
3
DI3
Autochange triggered by the rising edge of digital input DI3
(
, bit 2).
4
DI4
Autochange triggered by the rising edge of digital input DI4
(
, bit 3).
5
DI5
Autochange triggered by the rising edge of digital input DI5
(
, bit 4).
6
DI6
Autochange triggered by the rising edge of digital input DI6
(
, bit 5).
7
Timed function 1
Autochange triggered by timed function 1 (bit 0 of
(see page
)).
8
Timed function 2
Autochange triggered by timed function 2 (bit 1 of
(see page
)).
9
Timed function 3
Autochange triggered by timed function 3 (bit 2 of
(see page
)).
10
Fixed interval
Autochange is done when the interval determined in the
parameter
has elapsed.
11
No.
Name/Value
Description
Def/FbEq16
ACS580 FW.book Page 321 Wednesday, September 21, 2016 9:48 PM
Содержание ACS580 Series
Страница 88: ...84 ACS580 FW book Page 84 Wednesday September 21 2016 9 48 PM ...
Страница 146: ...142 Program features ACS580 FW book Page 142 Wednesday September 21 2016 9 48 PM ...
Страница 444: ...440 Fieldbus control through a fieldbus adapter ACS580 FW book Page 440 Wednesday September 21 2016 9 48 PM ...
Страница 461: ...ACS580 FW book Page 457 Wednesday September 21 2016 9 48 PM ...
Страница 462: ...3AXD0000016097 Rev D EN 2016 09 02 ACS580 FW book Page 458 Wednesday September 21 2016 9 48 PM ...