180
ACS510 User’s Manual
Fieldbus Adapter
* This parameter is not available in software N688 and +N689.
Input Reference Select
Using the fieldbus to provide input reference to the drive requires:
• Drive parameter value set as defined below.
• Fieldbus controller supplied reference word(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
Note!
Multiple references are supported only when using the ABB Drives profile.
Scaling
Where required,
REFERENCES
can be scaled. See the "Reference Scaling" in the
following sections, as appropriate:
• "ABB Drives Profile Technical Data"
• "Generic Profile Technical Data"
System Control
Using the fieldbus for miscellaneous drive control requires:
• Drive parameter values set as defined below.
• Fieldbus controller command(s) in the appropriate location. (The location is
defined by the Protocol Reference, which is protocol dependent.)
1002
EXT
2
COMMANDS
10 (
COMM
)
Start/Stop by controlled fieldbus with
Ext2 selected.
1003
*
DIRECTION
3 (
REQUEST
) Direction controlled by fieldbus.
Drive Parameter
Value
Description
Protocol
Reference
1102
EXT
1/
EXT
2
SEL
8 (
COMM
)
Ref. selected by fieldbus.
(Required only if 2 references used.)
1103
REF
1
SEL
8 (
COMM
)
9 (
COMM
+
AI
1)
10 (
COMM
*
AI
1)
Input reference 1 supplied by fieldbus.
1106
REF
2
SEL
8 (
COMM
)
9 (
COMM
+
AI
)
10 (
COMM
*
AI
)
Input reference 2 supplied by fieldbus.
(Required only if 2 references used.)
Drive Parameter
Value
Description
Protocol
Reference
1601
RUN
ENABLE
7 (
COMM
) Run enable by fieldbus.
1604
FAULT
RESET
SEL
8 (
COMM
) Fault reset by fieldbus.
Drive Parameter
Value
Description
Protocol
Reference