ACS510 User’s Manual
215
Technical Data
Fuses, 380…480 V Drives
Emergency Stop Devices
The overall design of the installation must include emergency stop devices and any
other safety equipment that may be needed. Pressing STOP on the drive’s control
panel does NOT:
• Generate an emergency stop of the motor.
• Separate the drive from dangerous potential.
Input Power Cables/ Wiring
Input wiring can be any of:
• A four conductor cable (three phases and ground/protective earth). Shielding is
not required.
• Four insulated conductors routed through conduit.
Size wiring according to local safety regulations, appropriate input voltage and the
drive’s load current. In any case, the conductor must be less than the maximum limit
defined by the terminal size (see "Drive’s Power Connection Terminals" on page
218).
ACS510-01-
see below
Input Current
A
Input power (mains) fuses
IEC 269 gG (A)
UL Class T (A)
Bussmann Type
-03A3-4
3.3
10
10
JJS-10
-04A1-4
4.1
-05A6-4
5.6
-07A2-4
7.2
-09A4-4
9.4
15
JJS-15
-012A-4
11.9
16
-017A-4
17
20
JJS-20
-025A-4
25
25
30
JJS-30
-031A-4
31
35
40
JJS-40
-038A-4
38
50
50
JJS-50
-046A-4
46
60
JJS-60
-060A-4
60
63
80
JJS-80
-072A-4
72
80
90
JJS-90
-088A-4
88
125
125
JJS-125
-125A-4
125
160
175
JJS-175
-157A-4
157
200
200
JJS-200
-180A-4
180
250
250
JJS-250
-195A-4
205
250
250
JJS-250
-246A-4
245
250
250
JJS-250
-290A-4
290
315
315
JJS-350