60
ACS510 User’s Manual
Start-Up
3705
LOAD
TORQ
LOW
1
0%...600%
1%
10%
3706
LOAD
TORQ
HIGH
1
0%...600%
1%
300%
3707
LOAD
FREQ
2
0...500 Hz
1 Hz
25 Hz
3708
LOAD
TORQ
LOW
2
0%...600%
1%
15%
3709
LOAD
TORQ
HIGH
2
0%...600%
1%
300%
3710
LOAD
FREQ
3
0...500 Hz
1 Hz
43 Hz
3711
LOAD
TORQ
LOW
3
0%...600%
1%
25%
3712
LOAD
TORQ
HIGH
3
0%...600%
1%
300%
3713
LOAD
FREQ
4
0...500 Hz
1 Hz
50 Hz
3714
LOAD
TORQ
LOW
4
0%...600%
1%
30%
3715
LOAD
TORQ
HIGH
4
0%...600%
1%
300%
3716
LOAD
FREQ
5
0...500 Hz
1 Hz
500 Hz
3717
LOAD
TORQ
LOW
5
0%...600%
1%
30%
3718
LOAD
TORQ
HIGH
5
0%...600%
1%
300%
Group 40: Process PID Set 1
4001
GAIN
0.1…100
0.1
2.5
4002
INTEGRATION
TIME
0.0s =
NOT
SEL
, 0.1…3600.0 s
0.1 s
3.0 s
4003
DERIVATION
TIME
0…10.0 s
0.1 s
0.0 s
4004
PID
DERIV
FILTER
0…10.0 s
0.1 s
1.0 s
4005
ERROR
VALUE
INV
0 =
NO
, 1 =
YES
-
0
4006
UNITS
0…127
1
4
4007
UNIT
SCALE
0…4
1
1
4008
0%
VALUE
Unit and scale defined by par. 4006 and
4007
-
0.0%
4009
100%
VALUE
Unit and scale defined by par. 4006 and
4007
-
100.0%
4010
SET
POINT
SEL
0…2, 8...17, 19, 20
1
1
9
4011
INTERNAL
SETPNT
Unit and scale defined by par. 4006 and
4007
0.1%
40.0%
4012
SETPOINT
MIN
-500.0%…500.0%
0.1%
0.0%
4013
SETPOINT
MAX
-500.0%…500.0%
0.1%
100.0%
4014
FBK
SEL
1…13
1
1
4015
FBK
MULTIPLIER
-32.768…32.767 (0 = not used)
0.001
0
4016
ACT
1
INPUT
1…7
1
2
9
4017
ACT
2
INPUT
1…7
1
2
9
4018
ACT
1
MINIMUM
-1000…1000%
1%
0%
4019
ACT
1
MAXIMUM
-1000…1000%
1%
100%
4020
ACT
2
MINIMUM
-1000…1000%
1%
0%
4021
ACT
2
MAXIMUM
-1000…1000%
1%
100%
4022
SLEEP
SELECTION
-6…7
1
0
4023
PID
SLEEP
LEVEL
0.0…500.0 Hz /
+N688:0.0...50.0 Hz /
+N689:0.0...55.0 Hz
0.1 Hz
0.0 Hz
4024
PID
SLEEP
DELAY
0.0…3600.0 s
0.1 s
60.0 s
4025
WAKE
-
UP
DEV
Unit and scale defined by par. 4006 and
4007
-
0.0%
Code
Name
Range
Resolution
Default
User S