58
ACS510 User’s Manual
Start-Up
2613
USER F
2
0.0…500.0 Hz /
+N688:0.0...50.0 Hz /
+N689:0.0...55.0 Hz
0.1 Hz
20.0 Hz /
+N688:20.0 Hz /
+N689:22.0 Hz
2614
USER U
3
0...480 V
1 V
228 V
2615
USER F
3
0.0…500.0 Hz /
+N688:0.0...50.0 Hz /
+N689:0.0...55.0 Hz
0.1 Hz
30.0 Hz /
+N688:30.0 Hz /
+N689:33.0 Hz
2616
USER U
4
0...480 V
1 V
304 V
2617
USER F
4
0.0…500.0 Hz /
+N688:0.0...50.0 Hz /
+N689:0.0...55.0 Hz
0.1 Hz
40.0 Hz /
+N688:40.0 Hz /
+N689:44.0 Hz
2618
FW VOLTAGE
190...480 V
1 V
380 V
2619
DC
STABILIZER
0…1
1
0
Group 30: Fault Functions
3001
AI
<
MIN
FUNCTION
0…3
1
0
3002
PANEL
COMM
ERR
1…3
1
1
3003
EXTERNAL
FAULT
1
-6…6
1
0
3004
EXTERNAL
FAULT
2
-6…6
1
0
3005
MOT
THERM
PROT
0 =
NOT
SEL
, 1 =
FAULT
, 2 =
WARNING
1
1 (
FAULT
)
3006
MOT
THERM
TIME
256…9999 s
1
1050 s
3007
MOT
LOAD
CURVE
50…150%
1
100%
3008
ZERO
SPEED
LOAD
25…150%
1
70%
3009
BREAK
POINT
FREQ
1…250 Hz
1
35 Hz
3010
STALL
FUNCTION
0…2
1
0 (
NOT
SEL
)
3011
STALL
FREQUENCY
0.5…50.0 Hz
0.1 Hz
20.0 Hz
3012
STALL
TIME
10…400 s
1 s
20 s
3017
EARTH
FAULT
0
=
DISABLE
, 1 =
ENABLE
1
1 (
ENABLE
)
3018
COMM
FAULT
FUNC
0 =
NOT
SEL
, 1 =
FAULT
, 2 =
CONST
SP
7,
3 =
LAST
SPEED
1
0 (
NOT
SEL
)
3019
COMM
FAULT
TIME
0.0…60.0 s
0.1 s
10.0 s
3021
AI
1
FAULT
LIMIT
0.0…100.0%
0.1%
0.0%
3022
AI
2
FAULT
LIMIT
0.0…100.0%
0.1%
0.0%
3023
WIRING
FAULT
0 =
DISABLE
, 1 =
ENABLE
1
1
3024
CB TEMP FAULT
0…1
1
1
Group 31: Automatic Reset
3101
NUMBER
OF
TRIALS
0…5
1
5
3102
TRIAL
TIME
1.0…600.0 s
0.1 s
30.0 s
3103
DELAY
TIME
0.0…120.0 s
0.1 s
6.0 s
3104
AR
OVERCURRENT
0 =
DISABLE
, 1 =
ENABLE
1
1
3105
AR
OVERVOLTAGE
0 =
DISABLE
, 1 =
ENABLE
1
1
3106
AR
UNDERVOLTAGE
0 =
DISABLE
, 1 =
ENABLE
1
1
3107
AR
AI
<
MIN
0 =
DISABLE
, 1 =
ENABLE
1
1
3108
AR
EXTERNAL
FLT
0 =
DISABLE
, 1 =
ENABLE
1
1
Group 32: Supervision
3201
SUPERV
1
PARAM
100…159
1
103
3202
SUPERV
1
LIM
LO
-
-
0
Code
Name
Range
Resolution
Default
User S
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd