ACS510 User’s Manual
59
Start-Up
3203
SUPERV
1
LIM
HI
-
-
0
3204
SUPERV
2
PARAM
100…159
1
104
3205
SUPERV
2
LIM
LO
-
-
0
3206
SUPERV
2
LIM
HI
-
-
0
3207
SUPERV
3
PARAM
100…159
1
105
3208
SUPERV
3
LIM
LO
-
-
0
3209
SUPERV
3
LIM
HI
-
-
0
Group 33: Information
3301
F
IRMWARE
0000...FFFF hex
1
Firmware version
3302
L
OADING PACKAGE
0000...FFFF hex
1
0
3303
TEST
DATE
yy.ww
1
0
3304
DRIVE
RATING
-
-
-
3305
PARAMETER TABLE
0000...FFFF hex
1
Par. table version
Group 34: Panel Display / Process Variables
3401
SIGNAL
1
PARAM
100...159
1
103
3402
SIGNAL
1
MIN
-
1
-
3403
SIGNAL
1
MAX
-
1
-
3404
OUTPUT
1
DSP
FORM
0…9
1
9
3405
OUTPUT
1
UNIT
0...127
1
.
3406
OUTPUT
1
MIN
-
1
-
3407
OUTPUT
1
MAX
-
1
-
3408
SIGNAL
2
PARAM
100...159
1
104
3409
SIGNAL
2
MIN
-
1
-
3410
SIGNAL
2
MAX
-
1
-
3411
OUTPUT
2
DSP
FORM
0…9
1
9
3412
OUTPUT
2
UNIT
0...127
1
-
3413
OUTPUT
2
MIN
-
1
-
3414
OUTPUT
2
MAX
-
1
-
3415
SIGNAL
3
PARAM
100...159
1
105
3416
SIGNAL
3
MIN
-
1
-
3417
SIGNAL
3
MAX
-
1
-
3418
OUTPUT
3
DSP
FORM
0…9
1
9
3419
OUTPUT
3
UNIT
0…127
1
.
3420
OUTPUT
3
MIN
-
1
-
3421
OUTPUT
3
MAX
-
1
-
Group 35: Motor Temp Meas
3501
SENSOR
TYPE
0…6
1
0
3502
INPUT
SELECTION
1…8
1
1
3503
ALARM
LIMIT
-10...200
°
C / 0...5000 Ohm / 0…1
1
110
°
C / 1500 Ohm / 0
3504
FAULT
LIMIT
-10...200
°
C / 0...5000 Ohm / 0…1
1
130
°
C / 4000 Ohm / 0
Group 37: User Adjustable Load Curves
3701
USER
LOAD
C
MODE
0…3
1
0
3702
USER
LOAD
C
FUNC
1…2
1
1
3703
USER
LOAD
C
TIME
10...400 s
1 s
20 s
3704
LOAD
FREQ
1
0...500 Hz
1 Hz
5 Hz
Code
Name
Range
Resolution
Default
User S
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd