Parameters in the Long parameter mode
Index
Name/Selection
Description
Def
45 ENERGY METER RESET
4509
ENERGY CONSUMPTION
(KWH) Meter Reset
0
No Function
0
1
Setting to 1 resets internal kWh meter to zero (as displayed in parameter 0115 ENERGY
CONSUMPTION KWH METER and parameter 0141 ENERGY CONSUMPTION MWH METER.
53 COMMUNICATIONS
PARAMETERS
5302
DRIVE FIELDBUS
ADDRESS
Sets the fieldbus address for the ACS255
1
0…63
5303
Modbus RTU Baud Rate
Sets the baud rate when Modbus RTU communications are used
115.2 kbps
9.6…115.2 kbps
5304
Modbus Data Format
Sets the expected Modbus telegram data format.
No Parity, 1 stop bit
No parity, 2 stop bits
Odd parity, 1 stop bit
Even parity, 1 stop bit
5305
CAN Open Baud Rate
Sets the baud rate when CAN Open communications are used
500 kbps
125…1000 kbps
99 START-UP DATA
Definition of motor set-up data.
9902
Digital Inputs
Function Select
Defines the function of the digital inputs depending on the control mode setting in
Parameter 1103 PRIMARY COMMAND SOURCE MODE.
1
9903
Motor Control Mode
Selects the motor control method. An autotune must be performed if setting 0, 1 or 3 is used.
2: Speed
Control
(Enhanced
V/F)
0: Speed Control with
Torque Limit (vector)
1: Torque Control with
Speed Limit (vector)
2: Speed Control
(Enhanced V/F)
3 : PM Vector
4 : Reserved
9905
MOTOR RATED VOLTAGE
This parameter should be set to the rated (nameplate) voltage of the motor (Volts).
Drive Rating
Dependent
0…660V
Voltage
Note : The stress on the motor insulation is always dependant on the drive supply voltage.
This also applies in the case where the motor voltage rating is lower than the rating of the
drive and the supply of the drive.
9906
MOTOR RATED CURRENT
This parameter should be set to the rated (nameplate) current of the motor.
Drive Rating
Dependent
0.2* drive rated output
current…1.0* drive rated
output current
Current
9907
MOTOR RATED FREQ
This parameter should be set to the rated (nameplate) frequency of the motor
60Hz
25…500Hz
Frequency
9908
MOTOR RATED SPEED
This parameter can optionally be set to the rated (nameplate) rpm of the motor. When set to
the default value of zero, all speed related parameters are displayed in Hz, and the slip
compensation for the motor is disabled. Entering the value from the motor nameplate
enables the slip compensation function, and the ACS255 display will now show motor speed
in estimated rpm. All speed related parameters, such as Minimum and Maximum Speed,
Preset Speeds etc. will also be displayed in Rpm.
0 Rpm
0…30000 Rpm
9910
MOTOR PARAMETER
AUTO-TUNE ENABLE
Drive measures the motor parameters for optimum control and efficiency. Following
completion of the autotune.
0 : DISABLE
0 : DISABLE
1: ENABLE
Drive immediately carries out a non-rotating autotune, parameter 9910 MOTOR PARAMETER
AUTO-TUNE ENABLE returns to 0 when completed.
9915
Motor Power Factor Cos
Ø
When operating in Vector Speed or Vector Torque motor control modes, this parameter must
be set to the motor nameplate power factor
-
0.00…0.99