Parameters in the Long parameter mode
Index
Name/Selection
Description
Def
1507
ANALOG OUTPUT 2
(TERMINAL 11) FUNCTION
SELECT
Selects the type of output signal information indicated from terminal 11.
Note :
When using settings 0 – 7 the output is a digital format (Logic 1 = 24V).
When using settings 8– 11 the output is an analog format.
Note : When using settings 4 – 7, parameters 3203 ADJUSTABLE THRESHOLD 1 UPPER LIMIT
and 3202 ADJUSTABLE THRESHOLD 1 LOWER LIMIT must be used together to control the
behaviour. The output will switch to Logic 1 when the selected signal exceeds the value
programmed in parameters 3203 ADJUSTABLE THRESHOLD 1 UPPER LIMIT, and return to
Logic 0 when the signal falls below the value programmed in 3202 ADJUSTABLE THRESHOLD
1 LOWER LIMIT.
9 : Output
(Motor)
Current.
0 : DRIVE ENABLED
(RUNNING)
Logic 1 when the ACS255 is enabled (Running)
1: DRIVE READY
Logic 1 When no Fault condition exists on the drive
2 : AT TARGET FREQUENCY
(SPEED).
Logic 1 when the output frequency matches the setpoint frequency
3 : OUTPUT FREQUENCY
> 0.0
Logic 1 when the motor runs above zero speed
4 : OUTPUT FREQUENCY
>= LIMIT
Logic 1 when the motor speed exceeds the adjustable limit. (See note above)
5 : OUTPUT CURRENT >=
LIMIT
Logic 1 when the motor current exceeds the adjustable limit. (See note above)
6 : MOTOR TORQUE >=
LIMIT
Logic 1 when the motor torque exceeds the adjustable limit. (See note above)
7 : ANALOG INPUT 2
SIGNAL LEVEL >= LIMIT.
Logic 1 when the signal applied to the Analog Input 2 exceeds the adjustable limit. (See note
above)
8 : OUTPUT FREQUENCY
(MOTOR SPEED).
0 to Parameter 2008 MAXIMUM FREQUENCY/SPEED LIMIT
9 : OUTPUT (MOTOR)
CURRENT.
0 to 200% of Parameter 9906 MOTOR RATED CURRENT
10 : MOTOR TORQUE.
0 to 200% of motor rated torque
11 : OUTPUT (MOTOR)
POWER
0 to 150% of drive rated power
1508
ANALOG OUTPUT 2
(TERMINAL 11) FORMAT
Selects the type of output signal from terminal 11
0 to 10V
10 to 0V
0 to 20mA
20 to 0mA
4 to 20mA
20 to 4mA
16 SYSTEM CONTROLS
Run enable, parameter lock etc.
1602
PARAMETER ACCESS
UNLOCK
If parameter 1603 PARAMETER ACCESS CODE DEFINITION has had a value entered, then the
matching value needs to be entered here in order to give read-write access to the
parameters.
0
0…65535
See section 9.5 for more details
1603
PARAMETER ACCESS CODE
DEFINITION
To make all parameters read-only (except parameter 1602 Parameter Access Unlock), enter a
value in this parameter.
0
0…65535
See section 9.5 for more details
20 LIMITS
Drive operation limits
2005
OVER VOLTAGE CURRENT
LIMIT
This parameter is only valid in vector speed control mode and will come into function once
the drive DC bus voltage increases above a preset limit
This voltage limit is set internally just below the over voltage trip level. This parameter will
effectively limit the output torque current in order to prevent a large current flowing back to
the drive, which may cause an Over-voltage trip. A small value in this parameter will limit the
motor control torque when the drive DC bus voltage exceeds the preset limit. A higher value
may cause a significant distortion in the motor current, which may cause an aggressive,
rough motor behaviour.
1.0%
0.0…100.0