![ABB ACS2000 AFE 2MVA Скачать руководство пользователя страница 46](http://html.mh-extra.com/html/abb/acs2000-afe-2mva/acs2000-afe-2mva_user-manual_3277046.webp)
CHAPTER 2 – POWER ELECTRONICS AND CABINET FEATURES
46
2.7.2 Function
Fan groups
For control reasons, the fan unit(s) of the drive and
the integrated transformer are combined to
groups, for example:
• Fan unit 1 of the drive and fan unit 1 of the inte-
grated transformer belong to group 1.
• Fan unit 2 of the drive and fan unit 2 of the inte-
grated transformer belong to group 2.
The fan units of a group are always switched on
and off together.
Starting, stopping
The standard fan group 1 is switched on by the
control system of the drive when charging of the
DC link is initiated. When the drive is stopped, the
fan group continues to run for a preset time after
the main power has been switched off and the DC-
link voltage has decreased below a preset value.
Operating intervals
Parameter setting allows to run one of the two
fans continuously, or to run the fans alternately in
adjustable intervals. The intervals are set with
parameters.
Air flow inside the drive
The fan group of the cabinet feeds the cooling air
to the main power electronic components and
transfers the heat to the outside of the cabinet.
!
For further information on settings for
the cooling system, see
signal and
parameter table
, section
automatic con
-
verter-fan change-over
.
—
References
—
2-17 Example for the
operating time of the fan
units
—
2-18 Air flow inside the
cabinet
—
72 h
72 h
24 h
24 h
Fan 1 or fan group 1
Fan 2 or fan group 2
on
on
off
off
—
Содержание ACS2000 AFE 2MVA
Страница 8: ...General information on manual and equipment ...
Страница 13: ...13 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Страница 14: ...Terms abbreviations trademarks ...
Страница 19: ...19 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Страница 20: ...Important note on main circuit breaker ...
Страница 48: ...Chapter 3 Control system 49 Control unit 50 Main components 55 I O interfaces ...
Страница 69: ...69 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Страница 111: ...111 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Страница 118: ...Commissioning check list ...
Страница 153: ...153 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Страница 180: ......