CHAPTER 6 – ELECTRICAL INSTALLATION
98
Preparing cables for EMC plates
The orientation of the EMC plates is the same for
top and bottom cable entry: the sealing grommets
face always upwards.
1. Remove the grommets.
2. To ensure proper sealing, cut along the marking
that corresponds to the cable diameter.
3. Slide the grommet onto the cable. The grom-
met must fit tightly to prevent water entering
the cabinet.
4. The grommets can be discarded if cables are
entered through the cabinet floor.
5. If necessary, remove the entry plate and push
the cable through the entry holes.
6. Prepare the cables as illustrated in
-
(A) illustrates how cables with an outer cable
screen or shield are prepared
for EMC bond-
ing with the metal enclosure of the cabinet.
-
(B) illustrates how cables
without an outer
screen or shield
are prepared
.
—
References
—
6-5 Preparing power
cables for EMC plates
—
Outer cable sheath
Grommet
Entry plate
EMC sleeve
Conductor insulation removed to expose
cable shield
Cable tie
Conductor screen extension to be
connected to PE ground busbar
Heat-shrinkable termination
1
2
3
4
5
6
7
8
A
B
1
2
3
4
5
6
7
8
Содержание ACS2000 AFE 2MVA
Страница 8: ...General information on manual and equipment ...
Страница 13: ...13 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Страница 14: ...Terms abbreviations trademarks ...
Страница 19: ...19 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Страница 20: ...Important note on main circuit breaker ...
Страница 48: ...Chapter 3 Control system 49 Control unit 50 Main components 55 I O interfaces ...
Страница 69: ...69 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Страница 111: ...111 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Страница 118: ...Commissioning check list ...
Страница 153: ...153 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Страница 180: ......