Air flow monitoring
Air pressure switches monitor the air flow through
the cabinet of the integrated transformer
and the cabinet of the drive
.
Separate air pressure switches in each cabinet
monitor the air flow through the filter mats and the
air flow through the cabinets.
When the filter mats are clogged and the pressure
drop reaches the specified final pressure loss, the
message
Conv1CoolAirFilter
is displayed on the
CDP control panel and the alarm-fault lamp lights
up on the control compartment door.
When a fan of the drive or a fan of the integrated
transformer fails, the control system of the drive
switches on the stand-by fan automatically. The
failure of a fan is indicated on the CDP control
panel of the drive as follows:
• CoolCircuit1Alm if a fan of the drive fails
• CoolCircuit2Alm if a fan of the integrated trans-
former fails
• The alarm fault lamp starts to flash.
—
References
—
2-19 Air pressure
switches
—
1
2
Содержание ACS2000 AFE 2MVA
Страница 8: ...General information on manual and equipment ...
Страница 13: ...13 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Страница 14: ...Terms abbreviations trademarks ...
Страница 19: ...19 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Страница 20: ...Important note on main circuit breaker ...
Страница 48: ...Chapter 3 Control system 49 Control unit 50 Main components 55 I O interfaces ...
Страница 69: ...69 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Страница 111: ...111 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Страница 118: ...Commissioning check list ...
Страница 153: ...153 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV H ...
Страница 180: ......