Appendix A – ACS/ACC/ACP 601 Technical Data
ACS/ACC/ACP 601 Drives
ACx=ACS/ACC/ACP
A-3
Rating table continued
Note:
The US manufactured units are labeled as -4 types. The information in
this manual concerning the corresponding -5 types applies to them.
Output Current
Temperature Derating
The output current is calculated by multiplying the current given in the
rating table by the derating factor.
Temperature derating factor for degree of protection IP 21/22:
•
General rule:
Above +40 °C (104 °F), the rated output current is
decreased 3.5 % for every additional 1 °C up to +50 °C (1.94% for
every additional 1 °F up to 122 °F).
•
Example 1.
If the ambient temperature is 50 °C the derating factor is
100 % - 3.5
· 10 °C = 65 % or 0.65. The output current is then
0.65 ·
I
2N
or
I
2hd
.
Derating factor for ACx 600 in Pump and Fan Use (I
Nsq
rating):
•
Above +40 °C (104 °F) (+35 °C/95 °F for ACx 601-120-03 units),
the rated output current is decreased 5 % for every additional 1 °C
up to +50 °C (2.78% for every additional 1 °F up to 122 °F).
Derating factor for ACx 601 with degree of protection IP 54:
•
From +25 °C (77°F) to +40 °C (104 °F), the output current is
calculated using the table below.
•
Above +40 °C (104 °F), the output current is decreased 3.5 % for
every additional 1 °C up to +50 °C (1.94% for every additinoal 1 °F
up to 122 °F).
•
Example 1
. If the ambient temperature is 38 °C, the derating factor
for ACx 601-0006-3 is 95 % or 0.95 (Curve 2). The output current is
then 0.95 ·
I
2N
or
I
2hd
.
Normal Use
Heavy-duty Use
ACx 601
Type
Duty Cycle
1/10 min
Duty Cycle
1/10 min
Duty Cycle
1)
2/15 s
Frame
Type
I
2N
9/10min
[A]
I
2Nmax
1/10min
[A]
P
N
[HP]
I
2hd
9/10min
[A]
I
2hdmax
1/10min
[A]
I
2hd
13/15s
[A]
I
2hdmax
2/15s
[A]
P
hd
[HP]
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
ACx 601-0006-4
7.6
8.4
5
6.2
9.3
6.2
12.4
3
R2
ACx 601-0009-4
11
12
7.5
7.6
11
7.6
15.2
5
ACx 601-0011-4
15
17
10
11
17
11
22
7.5
ACx 601-0016-4
21
23
15
15
23
15
30
10
R3
ACx 601-0020-4
27
30
20
19
27
19
36
10
ACx 601-0025-4
34
37
25
24
36
24
48
15
R4
ACx 601-0030-4
41
45
30
31
47
31
62
20
ACx 601-0040-4
52
57
40
41
62
41
82
30
R5
ACx 601-0050-4
65
72
50
47
71
47
94
30
ACx 601-0060-4
77
85
60
58
87
58
116
40
ACx 601-0070-4
96
106
75
68
98
68
130
50
R6
ACx 601-0100-4
124
136
100
86
126
86
168
60
ACx 601-0120-4
156
172
125
113
168
113
224
75
R7
ACx 601-0140-4
180
198
150
141
203
141
270
100
%
°C
Содержание ACS 601
Страница 4: ......
Страница 6: ......
Страница 14: ...Safety Instructions x ACx ACS ACC ACP ACS ACC ACP 601 Drives ...
Страница 18: ...xiv ACx ACS ACC ACP ACS ACC ACP Drives ...
Страница 22: ...Chapter 1 Introduction 1 4 ACx ACS ACC ACP ACS ACC ACP 601 Drives ...
Страница 26: ...Chapter 2 Mechanical Installation 2 4 ACx ACS ACC ACP ACS ACC ACP 601 Drives ...
Страница 40: ...Chapter 3 Electrical Installation 3 14 ACx ACS ACC ACP ACS ACC ACP 601 Drives ...
Страница 42: ...Chapter 4 Installation Checklist 4 2 ACx ACS ACC ACP ACS ACC ACP 601 Drives ...
Страница 44: ...Chapter 5 Maintenance 5 2 ACx ACS ACC ACP ACS ACC ACP 601 Drives ...
Страница 82: ...Appendix B ACS ACC ACP 601 Dimensional Drawings B 14 ACx ACS ACC ACP ACS ACC ACP 601 Drives ...
Страница 87: ......