Appendix C – IEC Installation
C-2
ACx=ACS/ACC/ACP
ACS/ACC/ACP 601 Drives
Motor Cable Shield
To effectively supress radiated and conducted radio-frequency
emissions, the shield conductivity must be at least 1/10 of the phase
conductor conductivity. One way of evaluating the effectiveness of the
shield is the shield inductance, which must be low and only slightly
dependent on the frequency. These requirements are easily met with a
copper or aluminium shield. The minimum requirement of the motor
cable shield of the ACx 600 is shown below. It consists of a concentric
layer of copper wires with an open helix of copper tape. The better and
tighter the shield is, the lower is the emission level and the bearing
currents.
Cable Routing
The motor cable should be installed away from other cable routes.
Motor cables of several drives can be run in parallel installed next to
each other. It is recommended that the motor cable, power cable and
control cables be installed on separate trays (minimum distance 500
mm (20”)). Long parallel runs of motor cable with other cables should
be avoided in order to decrease electromagnetic interference caused
by the rapid changes in the frequency converter output voltage.
Where control cables must cross power cables make sure they are
arranged at an angle as near to 90 degrees as possible. Extra cables
should not be run through the ACx 600.
The cable trays have good electrical bonding to each other and to the
grounding electrodes. Aluminium tray systems can be used to improve
local equalizing of potential.
Below is a diagram of cable routing.
Insulation jacket
Copper wire screen
Helix of copper tape
Cable core
Inner insulation
ACT
PAR
FUNC
DRIVE
ENTER
LOC
REM
RESET
REF
ACS 600
90 °
min 500 mm (20”)
Motor cable
Power cable
Control cables
min 300 mm (12”)
Содержание ACS 601
Страница 4: ......
Страница 6: ......
Страница 14: ...Safety Instructions x ACx ACS ACC ACP ACS ACC ACP 601 Drives ...
Страница 18: ...xiv ACx ACS ACC ACP ACS ACC ACP Drives ...
Страница 22: ...Chapter 1 Introduction 1 4 ACx ACS ACC ACP ACS ACC ACP 601 Drives ...
Страница 26: ...Chapter 2 Mechanical Installation 2 4 ACx ACS ACC ACP ACS ACC ACP 601 Drives ...
Страница 40: ...Chapter 3 Electrical Installation 3 14 ACx ACS ACC ACP ACS ACC ACP 601 Drives ...
Страница 42: ...Chapter 4 Installation Checklist 4 2 ACx ACS ACC ACP ACS ACC ACP 601 Drives ...
Страница 44: ...Chapter 5 Maintenance 5 2 ACx ACS ACC ACP ACS ACC ACP 601 Drives ...
Страница 82: ...Appendix B ACS ACC ACP 601 Dimensional Drawings B 14 ACx ACS ACC ACP ACS ACC ACP 601 Drives ...
Страница 87: ......