ACS/ACC/ACP 601 Drives
ACx=ACS/ACC/ACP
A-1
Appendix A – ACS/ACC/ACP 601 Technical Data
IEC Ratings for IP2/22
Enclosures
Below are the IEC ratings for ACS/ACC/ACP 601 with 50 Hz and 60 Hz
supplies. ACx = ACS/ACC/ACP. The 690 V series is not available for
ACP 600.
Symbols are described following the table.
The table continues on the next page
Normal Use
Heavy-duty Use
ACx 601
Type
Duty Cycle
1/10 min
Duty Cycle
1/10 min
Duty Cycle
1)
2/15 s
Frame
Size
I
2N
9/10min
[A]
I
2Nmax
1/10min
[A]
S
N
[kVA]
P
N
[kW]
P
N
[HP]
I
2hd
9/10min
[A]
I
2hdmax
1/10min
[A]
I
2hd
13/15s
[A]
I
2hdmax
2/15s
[A]
S
hd
[kVA]
P
hd
[kW]
P
hd
[HP]
Three-phase supply voltage 380 V, 400 V or 415 V
ACx 601-0005-3
7.6
8.4
5
3
3
6.2
9.3
6.2
12.4
4
2.2
3
R2
ACx 601-0006-3
11
12
6
4
5
7.6
11
7.6
15.2
5
3
3
ACx 601-0009-3
15
17
9
5.5
7.5
11
17
11
22
6
4
5
ACx 601-0011-3
18
20
11
7.5
10
15
23
15
30
9
5.5
7.5
R3
ACx 601-0016-3
24
26
16
11
15
18
27
18
36
11
7.5
10
ACx 601-0020-3
32
35
20
15
20
24
36
24
48
16
11
15
R4
ACx 601-0025-3
41
45
25
18.5
25
32
48
32
64
20
15
20
ACx 601-0030-3
47
52
30
22
30
41
62
41
82
25
18.5
25
R5
ACx 601-0040-3
62
68
40
30
40
47
71
47
94
30
22
30
ACx 601-0050-3
76
84
50
37
50
62
93
62
124
40
30
40
ACx 601-0060-3
89
98
60
45
60
76
114
76
152
50
37
50
R6
ACx 601-0070-3
112
123
70
55
75
89
134
89
178
60
45
60
ACx 601-0100-3
147
162
100
75
100
112
168
112
224
70
55
75
R7
ACx 601-0120-3
178
196
120
90
125
147
221
147
294
100
75
100
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
ACx 601-0006-5
7.6
8.4
6
4
5
6.2
9.3
6.2
12.4
5
3
3
R2
ACx 601-0009-5
11
12
9
5.5
7.5
7.6
11
7.6
15.2
6
4
5
ACx 601-0011-5
15
17
11
7.5
10
11
17
11
22
9
5.5
7.5
ACx 601-0016-5
18
20
16
11
10
15
23
15
30
11
7.5
10
R3
ACx 601-0020-5
24
26
20
15
15
18
27
18
36
16
11
10
ACx 601-0025-5
31
34
25
18.5
20
24
36
24
48
20
15
15
R4
ACx 601-0030-5
41
45
30
22
30
31
47
31
62
25
18.5
20
ACx 601-0040-5
47
52
40
30
30
41
62
41
82
30
22
30
R5
ACx 601-0050-5
58
64
50
37
40
47
71
47
94
40
30
30
ACx 601-0060-5
65
72
60
45
50
58
87
58
116
50
37
40
ACx 601-0070-5
84
92
70
55
60
65
98
65
130
60
45
50
R6
ACx 601-0100-5
112
123
100
75
75
84
126
84
168
70
55
60
ACx 601-0120-5
135
149
120
90
100
112
168
112
224
100
75
75
R7
ACx 601-0140-5
164
180
140
110
125
135
203
135
270
120
90
100
Three-phase supply voltage 525 V, 550 V, 575 V, 600 V, 660 V or 690 V
ACx 601-0009-6
7.6
11
9
5.5
7.5
6.2
9
6.2
9
6
4
5.0
R3
ACx 601-0011-6
11
12
11
7.5
10
7.6
11
7.6
11
9
5.5
7.5
ACx 601-0016-6
15
17
16
11
15
11
17
11
17
11
7.5
10
ACx 601-0020-6
20
22
20
15
20
15
23
15
23
16
11
15
ACx 601-0025-6
25
28
25
18.5
25
20
30
20
30
20
15
20
R4
ACx 601-0030-6
28
31
30
22
30
25
38
25
38
25
18.5
25
ACx 601-0040-6
36
40
40
30
40
28
42
28
42
30
22
30
R5
ACx 601-0050-6
44
48
50
37
50
36
54
36
54
40
30
40
ACx 601-0060-6
52
57
60
45
60
44
66
44
66
50
37
50
R6
ACx 601-0070-6
65
72
70
55
75
52
78
52
78
60
45
60
ACx 601-0100-6
88
97
100
75
100
65
98
65
98
70
55
75
R7
ACx 601-0120-6
105
116
120
90
125
88
132
88
132
100
75
100
Содержание ACS 601
Страница 4: ......
Страница 6: ......
Страница 14: ...Safety Instructions x ACx ACS ACC ACP ACS ACC ACP 601 Drives ...
Страница 18: ...xiv ACx ACS ACC ACP ACS ACC ACP Drives ...
Страница 22: ...Chapter 1 Introduction 1 4 ACx ACS ACC ACP ACS ACC ACP 601 Drives ...
Страница 26: ...Chapter 2 Mechanical Installation 2 4 ACx ACS ACC ACP ACS ACC ACP 601 Drives ...
Страница 40: ...Chapter 3 Electrical Installation 3 14 ACx ACS ACC ACP ACS ACC ACP 601 Drives ...
Страница 42: ...Chapter 4 Installation Checklist 4 2 ACx ACS ACC ACP ACS ACC ACP 601 Drives ...
Страница 44: ...Chapter 5 Maintenance 5 2 ACx ACS ACC ACP ACS ACC ACP 601 Drives ...
Страница 82: ...Appendix B ACS ACC ACP 601 Dimensional Drawings B 14 ACx ACS ACC ACP ACS ACC ACP 601 Drives ...
Страница 87: ......