38
ACS 400 User’s Manual
Table 6 Faults.
Fault Code
Display
Description
1
OVERCURRENT
Output current is excessive.
•
Motor load may be too high
•
Acceleration time may be too short (parameters 2201
ACCELER
TIME
1 and 2203
ACCELER
TIME
2).
•
Motor or motor cable is faulty or connected wrong.
2
DC
OVERVOLTAGE
Intermediate circuit DC voltage is excessive.
•
Check the input power supply for static or transient overvoltages
•
Deceleration time may be too short (parameters 2202
DECELER
TIME
1 and 2204
DECELER
TIME
2)
•
Brake chopper (if present) may be underdimensioned
3
ACS
400
OVERTEMP
ACS 400 heat sink temperature is excessive. Temperature trip limit is
95 °C.
•
Check air flow and fan operation.
•
Check motor power against unit power.
4 **
SHORT
CIRCUIT
Fault current. Possible reasons for this fault are:
•
There is a short-circuit in the motor cable(s) or motor
•
Supply disturbances
5
OUTPUT
OVERLOAD
Inverter overload condition. The ACS 400 output current exceeds the
ratings given in “Specifications” on page 21 of this manual.
6
DC
UNDERVOLTAGE
Intermediate circuit DC voltage is not sufficient.
•
Input power supply phase may be missing
•
Fuse may be blown
7
ANALOGUE
INPUT
1
Analog input 1 loss. Analog input value is less than
MINIMUM
AI
1 (1301).
See also parameter 3001
AI
<
MIN FUNCTION
.
8
ANALOGUE
INPUT
2
Analog input 2 loss. Analog input value is less than
MINIMUM
AI
2 (1306).
See also parameter 3001
AI
<
MIN FUNCTION
.
9
MOTOR
OVERTEMP
Motor overtemperature condition as estimated by the ACS 400. Refer
to parameters 3004 – 3008.
10
PANEL
LOSS
Panel communication loss. Control panel is disconnected when the
drive is receiving start, stop and direction commands from the panel.
- Drive is in local control mode (LOC is shown in the control panel
display), or
- Drive is in remote control mode (REM is shown) and is programmed to
accept start/stop, direction or reference from the panel. Refer to
parameters in groups 10 COMMAND INPUTS and 11 REFERENCE
SELECT.
See also parameter 3002
PANEL
LOSS
.
11
PARAMETERING
Parameter values are inconsistent:
•
MINIMUM
AI
1 >
MAXIMUM
AI
1 (parameters 1301, 1302)
•
MINIMUM
AI
2 >
MAXIMUM
AI
2 (parameters 1304, 1305)
•
MINIMUM
FREQ
>
MAXIMUM
FREQ
(parameters 2007, 2008)
•
PFC block tries to use the I/O extension module (NDIO) but the
DDCS link is not programmed properly
12
MOTOR
STALL
Motor stall. This may be caused by excessive load or insufficient motor
power. Refer to parameters 3009 – 3012.
13
SERIAL
COMM
LOSS
Serial communication through Standard Modbus Channel is lost.
•
Check connections between external control system and the
ACS 400.
•
Refer to parameters 5003
COMM
FAULT
TIME
and 5004
COMM
FAULT
FUNC
.
14
EXTERNAL
FAULT
SIGNAL
External fault is active. See parameter 3003
EXTERNAL
FAULT
.
15 **
OUTPUT
EARTH
FAULT
Ground fault. The load on the input power system is out of balance.
•
There may be a fault in the motor or motor cable.
•
Motor cable may be too long.
http://nicontrols.com
Содержание ACS 400
Страница 3: ...http nicontrols com ...
Страница 5: ...http nicontrols com ...
Страница 7: ...iv ACS 400 User s Manual http nicontrols com ...
Страница 45: ...34 ACS 400 User s Manual http nicontrols com ...
Страница 52: ...ACS 400 User s Manual 41 Motor Will Not Run http nicontrols com ...
Страница 53: ...42 ACS 400 User s Manual Motor Stalls during Acceleration http nicontrols com ...
Страница 54: ...ACS 400 User s Manual 43 Overvoltage Fault Indication http nicontrols com ...
Страница 55: ...44 ACS 400 User s Manual Overcurrent Fault Indication http nicontrols com ...
Страница 56: ...ACS 400 User s Manual 45 Overload Fault Indication http nicontrols com ...
Страница 57: ...46 ACS 400 User s Manual Undervoltage Fault Indication http nicontrols com ...
Страница 58: ...ACS 400 User s Manual 47 External Fault Indication http nicontrols com ...
Страница 59: ...48 ACS 400 User s Manual No Operator Display http nicontrols com ...
Страница 75: ...64 ACS 400 User s Manual http nicontrols com ...
Страница 161: ...150 ACS 400 User s Manual http nicontrols com ...
Страница 167: ...156 ACS 400 User s Manual http nicontrols com ...
Страница 177: ...166 ACS 400 User s Manual http nicontrols com ...
Страница 179: ...168 ACS 400 User s Manual ACS 400 NEMA Type 1 Enclosure R2 Frame Size http nicontrols com ...
Страница 180: ...ACS 400 User s Manual 169 ACS 400 NEMA Type 1 Enclosure R3 Frame Size http nicontrols com ...
Страница 181: ...170 ACS 400 User s Manual ACS 400 NEMA Type 1 Enclosure R4 Frame Size http nicontrols com ...
Страница 182: ...ACS 400 User s Manual 171 ACS 400 NEMA Type 12 4 Enclosure R1 Frame Size http nicontrols com ...
Страница 183: ...172 ACS 400 User s Manual ACS 400 NEMA 12 4 Enclosure R2 Frame Size http nicontrols com ...
Страница 184: ...ACS 400 User s Manual 173 ACS 400 NEMA Type 12 4 R3 Frame Size http nicontrols com ...
Страница 185: ...174 ACS 400 User s Manual ACS 400 NEMA Type 12 4 R4 Frame Size http nicontrols com ...
Страница 186: ...http nicontrols com ...