Planning the electrical installation
Power factor compensation capacitors
Power factor compensation is not needed with AC drives. However, if a drive is to be
connected in a system with compensation capacitors installed, note the following
restrictions.
WARNING!
Do not connect power factor compensation capacitors to the motor
cables (between the drive and the motor). They are not intended for use with AC
drives and can cause permanent damage to the drive or themselves.
If there are power factor compensation capacitors in parallel with the 3-phase input
of the drive:
1. Do not connect a high-power capacitor to the power line while the drive is
connected. The connection will cause voltage transients that may trip or even
damage the drive.
2. If capacitor load is increased/decreased step by step when the AC drive is
connected to the power line, ensure that the connection steps are low enough not
to cause voltage transients that would trip the drive.
3. Check that the power factor compensation unit is suitable for use in systems with
AC drives i.e. harmonic generating loads. In such systems, the compensation unit
should typically be equipped with a blocking reactor or harmonic filter.
Equipment connected to the motor cable
Installation of safety switches, contactors, connection boxes, etc.
To minimize the emission level when safety switches, contactors, connection boxes
or similar equipment are installed in the motor cable between the drive and the
motor:
• EU: Install the equipment in a metal enclosure with 360 degrees grounding for the
shields of both the incoming and outgoing cables, or in another way connect the
shields of the cables together.
• US: Install the equipment in a metal enclosure in a way that the conduit or motor
cable shielding runs consistently without breaks from the drive to the motor.
Bypass connection
WARNING!
Never connect the supply power to the drive output terminals U2, V2
and W2. If frequent bypassing is required, employ mechanically connected switches
or contactors. Mains (line) voltage applied to the output can result in permanent
damage to the unit.
Содержание ACQ800 Series
Страница 1: ...Hardware Manual ACQ800 37 Drives 55 to 450 kW 75 to 550 hp ACQ800 ...
Страница 4: ......
Страница 12: ...12 ACQ800 37 Hardware Manual Safety instructions ...
Страница 24: ...24 ACQ800 37 Hardware Manual About this manual ...
Страница 52: ...52 ACQ800 37 Hardware Manual Mechanical installation ...
Страница 78: ...78 ACQ800 37 Hardware Manual Electrical installation ...
Страница 84: ...84 ACQ800 37 Hardware Manual Motor control and I O board RMIO ...
Страница 92: ...92 ACQ800 37 Hardware Manual Installation checklist and start up ...
Страница 106: ...106 ACQ800 37 Hardware Manual Maintenance 3 4 5 6 8 7b 7a ...
Страница 107: ...ACQ800 37 Hardware Manual 107 Maintenance 9 10 11 View from back ...
Страница 123: ...ACQ800 37 Hardware Manual 123 Technical data Declaration of Conformity ...
Страница 124: ...124 ACQ800 37 Hardware Manual Technical data ...
Страница 128: ...128 ACQ800 37 Hardware Manual Dimensions Frame R6 ...
Страница 129: ...ACQ800 37 Hardware Manual 129 Dimensions Frame R6 continued ...
Страница 130: ...130 ACQ800 37 Hardware Manual Dimensions Frame R7i ...
Страница 131: ...ACQ800 37 Hardware Manual 131 Dimensions Frame R7i continued ...
Страница 132: ...132 ACQ800 37 Hardware Manual Dimensions Frame R7i continued ...
Страница 133: ...ACQ800 37 Hardware Manual 133 Dimensions Frame R7i continued ...
Страница 134: ...134 ACQ800 37 Hardware Manual Dimensions Frame R8i ...
Страница 135: ...ACQ800 37 Hardware Manual 135 Dimensions Frame R8i continued ...
Страница 136: ...136 ACQ800 37 Hardware Manual Dimensions Frame R8i continued ...
Страница 137: ...ACQ800 37 Hardware Manual 137 Dimensions Frame R8i continued ...
Страница 138: ...138 ACQ800 37 Hardware Manual Dimensions ...