ACQ800-37 Hardware Manual
59
Planning the electrical installation
Selecting the power cables
General rules
Dimension the supply (input power) and motor cables
according to local
regulations
:
• The cable must be able to carry the drive load current. See chapter
for the rated currents.
• The cable must be rated for at least 70
°
C maximum permissible temperature of
conductor in continuous use. For US, see
on
page
• The inductance and impedance of the PE conductor/cable (grounding wire) must
be rated according to permissible touch voltage appearing under fault conditions
(so that the fault point voltage will not rise excessively when a ground fault
occurs).
• 600 V AC cable is accepted for up to 500 V AC.
We recommend shielded symmetrical multicore cables for input cabling. Single-core
cables are also allowed, but unshielded single-core cables are not on IT
(ungrounded) networks.
WARNING!
Do not use unshielded single-core supply cables in IT (ungrounded)
networks. A dangerous voltage can become present on the non-conductive outer
sheath of the cable. This can cause injury or death.
Symmetrical shielded cable must be used for motor cabling; see section
Note:
When continuous conduit is employed, shielded cable is not required.
To operate as a protective conductor, the shield conductivity must be as follows
when the protective conductor is made of the same metal as the phase conductors:
Compared to a four-conductor system, the use of symmetrical shielded cable
reduces electromagnetic emission of the whole drive system as well as motor
bearing currents and wear.
Note:
The cabinet configuration of the drive may require multiple supply and/or
motor cabling. Refer to the connection diagrams in
The motor cable and its PE pigtail (twisted screen) should be kept as short as
possible in order to reduce electromagnetic emission as well as capacitive current.
Cross-sectional area of the phase
conductors
S (mm
2
)
Minimum cross-sectional area of the
corresponding protective conductor
S
p
(mm
2
)
S < 16
S
16 < S < 35
16
35 < S
S/2
Содержание ACQ800 Series
Страница 1: ...Hardware Manual ACQ800 37 Drives 55 to 450 kW 75 to 550 hp ACQ800 ...
Страница 4: ......
Страница 12: ...12 ACQ800 37 Hardware Manual Safety instructions ...
Страница 24: ...24 ACQ800 37 Hardware Manual About this manual ...
Страница 52: ...52 ACQ800 37 Hardware Manual Mechanical installation ...
Страница 78: ...78 ACQ800 37 Hardware Manual Electrical installation ...
Страница 84: ...84 ACQ800 37 Hardware Manual Motor control and I O board RMIO ...
Страница 92: ...92 ACQ800 37 Hardware Manual Installation checklist and start up ...
Страница 106: ...106 ACQ800 37 Hardware Manual Maintenance 3 4 5 6 8 7b 7a ...
Страница 107: ...ACQ800 37 Hardware Manual 107 Maintenance 9 10 11 View from back ...
Страница 123: ...ACQ800 37 Hardware Manual 123 Technical data Declaration of Conformity ...
Страница 124: ...124 ACQ800 37 Hardware Manual Technical data ...
Страница 128: ...128 ACQ800 37 Hardware Manual Dimensions Frame R6 ...
Страница 129: ...ACQ800 37 Hardware Manual 129 Dimensions Frame R6 continued ...
Страница 130: ...130 ACQ800 37 Hardware Manual Dimensions Frame R7i ...
Страница 131: ...ACQ800 37 Hardware Manual 131 Dimensions Frame R7i continued ...
Страница 132: ...132 ACQ800 37 Hardware Manual Dimensions Frame R7i continued ...
Страница 133: ...ACQ800 37 Hardware Manual 133 Dimensions Frame R7i continued ...
Страница 134: ...134 ACQ800 37 Hardware Manual Dimensions Frame R8i ...
Страница 135: ...ACQ800 37 Hardware Manual 135 Dimensions Frame R8i continued ...
Страница 136: ...136 ACQ800 37 Hardware Manual Dimensions Frame R8i continued ...
Страница 137: ...ACQ800 37 Hardware Manual 137 Dimensions Frame R8i continued ...
Страница 138: ...138 ACQ800 37 Hardware Manual Dimensions ...