MIN TORQUE SEL
-6…7
Defines control of the selection between two minimum torque limits
(2015
MIN
TORQUE
1 and 2016
MIN
TORQUE
2).
0 =
MIN
TORQUE
1 – Selects 2015
MIN
TORQUE
1 as the minimum limit
used.
1 =
DI
1 – Defines digital input
DI
1 as the control for selecting the
minimum limit used.
• Activating the digital input selects
MIN
TORQUE
2 value.
• De-activating the digital input selects
MIN
TORQUE
1 value.
2…6 =
DI
2…
DI
6 – Defines digital input
DI
2…
DI
6 as the control for
selecting the minimum limit used.
• See
DI
1 above.
7 =
COMM
– Defines bit 15 of Command Word 1 (parameter 0301) as the
control for selecting the minimum limit used.
• The Command Word is supplied through fieldbus communication.
-1 =
DI
1(
INV
) – Defines an inverted digital input
DI
1 as the control for
selecting the minimum limit used.
• Activating the digital input selects
MIN
TORQUE
1 value.
• De-activating the digital input selects
MIN
TORQUE
2 value.
-2…-6 =
DI
2(
INV
)…
DI
6(
INV
) – Defines an inverted digital input
DI
2…
DI
6
as the control for selecting the minimum limit used.
• See
DI
1(
INV
) above.
2014
MAX TORQUE SEL
-6…7
Defines control of the selection between two maximum torque limits
(2017
MAX
TORQUE
1 and 2018
MAX
TORQUE
2).
0 =
MAX
TORQUE
1 – Selects 2017
MAX
TORQUE
1 as the maximum limit
used.
1 =
DI
1 – Defines digital input
DI
1 as the control for selecting the
maximum limit used.
• Activating the digital input selects
MAX
TORQUE
2 value.
• De-activating the digital input selects
MAX
TORQUE
1 value.
2…6 =
DI
2…
DI
6 – Defines digital input
DI
2…
DI
6 as the control for
selecting the maximum limit used.
• See
DI
1 above.
7 =
COMM
– Defines bit 15 of Command Word 1 (parameter 0301) as the
control for selecting the maximum limit used.
• The Command Word is supplied through fieldbus communication.
-1 =
DI
1(
INV
) – Defines an inverted digital input di1 as the control for
selecting the maximum limit used.
• Activating the digital input selects
MAX
TORQUE
1 value.
• De-activating the digital input selects
MAX
TORQUE
2 value.
-2…-6 =
DI
2(
INV
)…
DI
6(
INV
) – Defines an inverted digital input
DI
2…
DI
6
as the control for selecting the maximum limit used.
• See
DI
1(
INV
) above.
Code Description
Range
Содержание ACH550-01
Страница 1: ...ACH550 User s Manual ACH550 01 Drives 0 75 110 kW ACH550 UH Drives 1 150 HP ABB ...
Страница 10: ...Update Notice 8 ...
Страница 12: ......
Страница 18: ...6 ACH550 User s Manual ...
Страница 50: ...38 Preparing for installation ACH550 User s Manual ...
Страница 325: ...313 ACH550 User s Manual ...
Страница 358: ...346 ACH550 User s Manual ...
Страница 409: ...Technical data 397 ACH550 User s Manual Frame size R1 IP54 UL Type 12 ...
Страница 410: ...398 Technical data ACH550 User s Manual Frame size R2 IP54 UL Type 12 ...
Страница 411: ...Technical data 399 ACH550 User s Manual Frame size R3 IP54 UL Type 12 ...
Страница 412: ...400 Technical data ACH550 User s Manual Frame size R4 IP54 UL Type 12 ...
Страница 413: ...Technical data 401 ACH550 User s Manual Frame size R5 IP54 UL Type 12 ...
Страница 414: ...402 Technical data ACH550 User s Manual Frame size R6 IP54 UL Type 12 ...
Страница 415: ...Technical data 403 ACH550 User s Manual Frame size R1 IP21 UL Type 1 ...
Страница 416: ...404 Technical data ACH550 User s Manual Frame size R2 IP21 UL Type 1 ...
Страница 417: ...Technical data 405 ACH550 User s Manual Frame size R3 IP21 UL Type 1 ...
Страница 418: ...406 Technical data ACH550 User s Manual Frame size R4 IP21 UL Type 1 ...
Страница 419: ...Technical data 407 ACH550 User s Manual Frame size R5 IP21 UL Type 1 ...
Страница 420: ...408 Technical data ACH550 User s Manual Frame size R6 IP21 UL Type 1 ...
Страница 453: ......