Parameter listing and descriptions
ACH550 User's Manual
14 =
AT
SET
POINT
– Energize the relay when the output frequency is
equal to the reference frequency.
15 =
FAULT
(
RST
) – Energize the relay when the drive is in a fault
condition and will reset after the programmed auto-reset delay.
• See parameter 3103
DELAY
TIME
.
16 =
FLT
/
ALARM
– Energize the relay when a fault or alarm occurs.
17 =
EXT
CTRL
– Energize the relay when external control is selected.
18 =
REF
2
SEL
– Energize the relay when
EXT
2 is selected.
19 =
CONST
FREQ
– Energize the relay when a constant speed is
selected.
20 =
REF
LOSS
– Energize the relay when the reference or active control
location is lost.
21 =
OVERCURRENT
– Energize the relay when an overcurrent alarm or
fault occurs.
22 =
OVERVOLTAGE
– Energize the relay when an overvoltage alarm or
fault occurs.
23 =
DRIVE
TEMP
– Energize the relay when a drive or control board
overtemperature alarm or fault occurs.
24 =
UNDERVOLTAGE
– Energize the relay when an undervoltage alarm
or fault occurs.
25 =
AI
1
LOSS
– Energize the relay when
AI
1 signal is lost.
26 =
AI
2
LOSS
– Energize the relay when
AI
2 signal is lost.
27 =
MOTOR
TEMP
– Energize the relay when a motor overtemperature
alarm or fault occurs.
28 =
STALL
– Energize the relay when a stall alarm or fault exists.
29 =
UNDERLOAD
– Energize the relay when an underload alarm or fault
occurs.
30 =
PID
SLEEP
– Energize the relay when the PID sleep function is
active.
31 = PFA – Use the relay to start/stop motor in PFA control (See
).
• Use this option only when PFA control is used.
• Selection activated / deactivated when the drive is not running.
32 =
AUTOCHANGE
– Energize the relay when PFA autochange operation
is performed.
• Use this option only when PFA control is used.
33 =
FLUX
READY
– Energize the relay when the motor is magnetized
and able to supply nominal torque (the motor has reached nominal
magnetizing).
34 =
USER
S
2 – Energize the relay when User Parameter Set 2 is active.
Code Description
Range
Содержание ACH550-01
Страница 1: ...ACH550 User s Manual ACH550 01 Drives 0 75 110 kW ACH550 UH Drives 1 150 HP ABB ...
Страница 10: ...Update Notice 8 ...
Страница 12: ......
Страница 18: ...6 ACH550 User s Manual ...
Страница 50: ...38 Preparing for installation ACH550 User s Manual ...
Страница 325: ...313 ACH550 User s Manual ...
Страница 358: ...346 ACH550 User s Manual ...
Страница 409: ...Technical data 397 ACH550 User s Manual Frame size R1 IP54 UL Type 12 ...
Страница 410: ...398 Technical data ACH550 User s Manual Frame size R2 IP54 UL Type 12 ...
Страница 411: ...Technical data 399 ACH550 User s Manual Frame size R3 IP54 UL Type 12 ...
Страница 412: ...400 Technical data ACH550 User s Manual Frame size R4 IP54 UL Type 12 ...
Страница 413: ...Technical data 401 ACH550 User s Manual Frame size R5 IP54 UL Type 12 ...
Страница 414: ...402 Technical data ACH550 User s Manual Frame size R6 IP54 UL Type 12 ...
Страница 415: ...Technical data 403 ACH550 User s Manual Frame size R1 IP21 UL Type 1 ...
Страница 416: ...404 Technical data ACH550 User s Manual Frame size R2 IP21 UL Type 1 ...
Страница 417: ...Technical data 405 ACH550 User s Manual Frame size R3 IP21 UL Type 1 ...
Страница 418: ...406 Technical data ACH550 User s Manual Frame size R4 IP21 UL Type 1 ...
Страница 419: ...Technical data 407 ACH550 User s Manual Frame size R5 IP21 UL Type 1 ...
Страница 420: ...408 Technical data ACH550 User s Manual Frame size R6 IP21 UL Type 1 ...
Страница 453: ......