120
120
4
2
3
1
4
2
3
1
+24 V
0 V
5
6
7
9
11
5
7
12
13
8
10
Fig. 115: DeviceNet interface, bus terminating resistors connected to the line ends
6
DeviceNet power supply
7
COMBICON connection, DeviceNet interface
8
Data lines, twisted pair cables
9
red
10
black
11
white
12
blue
13
bare
The earthing of the shield should take place at the switch-gear. Please refer to
Chapter 2.6.1 “System Data AC500” on page 1248.
Table 109: Assignment of the terminals
Terminal
Signal
Description
1.0
CAN+
Non-inverted signal of the CAN Bus
1.1
CAN+
Non-inverted signal of the CAN Bus
1.2
CAN-
Inverted signal of the CAN Bus
1.3
CAN-
Inverted signal of the CAN Bus
1.4
Term+
CAN bus termination for CAN+ (for bus termination,
Term+ must be connected with CAN+)
1.5
Term+
CAN bus termination for CAN+ (connecting alterna-
tive for terminal 1.4)
Mounting on
Terminal Units
TU517 or TU518
Device Specifications
Communication Interface Modules (S500) > CANopen
2019/04/17
3ADR010121, 13, en_US
706