Parameter
Value
Output current
≤
10 mA
Switching frequency
< 1 Mhz (depending on firmware)
Short-circuit-proof / overload-proof
Yes
Overload message (I > 0.1x A)
Yes, after ca. 100 ms
Output current limitation
Yes, automatic reactivation after short-circuit/
overload
Resistance to feedback against 24V signals
Yes
Resistance to feedback against reverse
polarity
No
Max. cable length (shielded)
100 m
Parameter
Value
Number of supplies
2, independently configuration
Voltage supply (outputs unloaded)
5 VDC +/- 5%
Resistance to feedback against reverse
polarity
No
Output current
100 mA max. (independently)
200 mA max. (parallel use)
Output diagnosis
Yes, with diagnosis LED and error message
Parameter
Value
Number of reference inputs (internally con-
nected to ZP through internal fuse)
6
Max. current per connection
0.5 A
Internal fuse protection
Terminals 1.4 and 1.6
2 A
Terminals 3.4 to 3.7
2 A
1.6.2.1.10
Ordering Data
Part No.
Description
Product Life Cycle Phase *)
1SAP 260 300 R0001 CD522, encoder & PWM module,
2 encoder inputs, 2 PWM outputs,
2 digital inputs 24 VDC, 8 digital
outputs 24 VDC
Active
1SAP 460 300 R0001 CD522-XC, encoder & PWM module,
2 encoder inputs, 2 PWM outputs,
2 digital inputs 24 VDC, 8 digital
outputs 24 VDC, XC version
Active
*) For planning and commissioning of new installations use modules in Active
status only.
Technical Data
of the 5 V
Sensor Supply
Technical Data
of the 0 V Refer-
ence Input
Device Specifications
Function Modules > S500
2019/04/17
3ADR010121, 13, en_US
674