Electromagnetic Compatibility
Test voltage
3V zone B, 10 V is also met.
High energy surges
According to IEC 61000-4-5, zone B,
criterion B
Power supply DC
1 kV CM / 0.5 kV DM
²
)
DC I/O supply
0.5 kV CM / 0.5 kV DM
²
)
Communication Lines, shielded
1 kV CM
²
)
AC I/O unshielded
2 kV CM / 1 kV DM
²
)
I/O analog, I/O DC unshielded
1 kV CM / 0.5 kV DM
²
)
Radiation (radio disturbance)
According to IEC 55011, group 1, class
A
1
) High requirement for shipping classes are achieved with additional specific measures (see
specific documentation).
²
) CM = Common Mode, DM = Differential Mode
2.6.1.6
Mechanical Data
Parameter
Value
Mounting
Horizontal
Degree of protection
IP 20
Housing
Classification V-2 according to UL 94
Vibration resistance acc. to EN 61131-2
all three axes
2 Hz...8.4 Hz, continuous 3.5 mm
8.4 Hz...150 Hz, continuous 1 g (higher values
on request)
Shock test
All three axes
15 g, 11 ms, half-sinusoidal
Mounting of the modules:
DIN rail according to DIN EN 50022
35 mm, depth 7.5 mm or 15 mm
Mounting with screws
Screws with a diameter of 4 mm
Fastening torque
1.2 Nm
2.6.1.7
Approvals and certifications
Information on approvals and certificates can be found in the corresponding chapter of the
2.6.2 Mechanical Dimensions
2.6.2.1
Switchgear Cabinet Assembly
Information on EMC-conforming assembly and construction is provided within
Chapter 2.4.4 “EMC-Conforming Assembly and
System Assembly, Construction and Connection
AC500 (Standard) > Mechanical Dimensions
2019/04/17
3ADR010121, 13, en_US
1252