LED
Color
State
Description
Blinking
Device sends/receives frames
Off
---
1.3.8.1.5 Technical Data
The System Data of AC500 and S500
Chapter 2.6.1 “System Data AC500” on page 1248
valid for standard version.
The System Data of AC500-XC
Chapter 2.7.1 “System Data AC500-XC” on page 1309
are
valid for the XC version.
Only additional details are therefore documented below.
Parameter
Value
Protocol
PROFINET I/O RT
Bus connection
2 x RJ45 (PNIO1 and PNIO2), with integrated
2-port switch
Switch
Integrated
Technology
Hilscher netX100
Transfer rate
100 Mbit/s (full-duplex)
Transfer method
According to Ethernet II, IEE802.3
Ethernet
100 base-TX, internal switch, 2x RJ45 socket
Bus length (segment length max.)
100 m
Indicators
5 LEDs
Usable terminal bases
All
Supported alarm types
Process alarm, diagnostic alarm, return of
SubModule, plug alarm, pull alarm
Alarm processing
Requires handling in application program
Current consumption from 24 VDC power
supply at the terminal base of the CPU
Typ. 85 mA
Internal supply
Via the communication module interface of the
terminal base
Weight
Ca. 170 g
Supported protocols
RTC - real-time cyclic protocol, class 1
RTA - real-time acyclic protocol
DCP - discovery and configuration protocol *)
CL-RPC - connectionless remote procedure
call
Since revision FW 2.4.8.0 additionally
LLDP - link layer discovery protocol
SNMP - simply network management protocol
(SNMP v1)
Acyclic services
PNIO read / write (max. 1392 bytes per tele-
gram, max. 4096 bytes per service request)
Device Specifications
Communication Modules (AC500 Standard) > PROFINET
2019/04/17
3ADR010121, 13, en_US
138