Flat Cable
Section 2 Transmission Media and Components
38
9ARD000015-600
lists the topology details of Flat cable.
Bend Radius
10 x thickness (installation and fixed)
Operating ambient
temperature
-25° C .. +75° C @ 1.5 amps; de-rate electric
current linearly to zero @ 80° C
Storage temperature
-40° C .. +85° C
Pull tension
90 lbs maximum
Durometer
95 Shore A (maximum)
Connector Compatibility
Flat
Topology Compatibility
Trunk
Table 32. Flat Cable Topology
Data Rate
Max
Cable
Distance
Trunk
Exchange
(Thick Cable)
Cumulative
Drop
Maximum
Drop
125 kb
420 m (1378 ft)
N/A
156 m (512 ft)
6 m (20 ft)
250 kb
200 m (656 ft)
N/A
78 m (256 ft)
6 m (20 ft)
500 kb
75 m (246 ft)
N/A
39 m (128 ft)
6 m (20 ft)
Table 31. Environmental Characteristics of General Specification for Flat Cables (Continued)
Applicable Environmental
Characteristics
Specification