![background image](http://html.mh-extra.com/html/abb/ac-800m/ac-800m_installation-manual_2907036.webp)
Flat Cable
Section 2 Transmission Media and Components
36
9ARD000015-600
Table 26. Electrical Characteristics of Data Pair Specification for Flat Cable
Electrical Characteristics
Specification
Impedance
120 ohms +/- 10% (at 500 MHz)
Propagation delay
1.60 nSec/ft (maximum)
Capacitance between conductors
N/A
Capacitive unbalance
1.2 pF/ft at 500 kHz (nominal)
ASTMD4566-94
DCR - @ 20° C
4.9 ohms/1000 ft (maximum)
Attenuation
0.13 db/100 ft @ 125 kHz (maximum)
0.25 db/100 ft @ 250 kHz (maximum)
0.40 db/100 ft @ 500 KHz (maximum)
Table 27. Physical Characteristics of DC Power Specification for Flat Cables
Physical Characteristics
Specification
Conductor pair
Size #16 Copper (minimum); 19 strands
minimum (individually tinned).
Insulation diameter
0.110 inches (nominal).
Colors Red
Black
pair/Twist/ft
N/A
Tape shield over pair
N/A