Network Components
Section 2 Transmission Media and Components
46
9ARD000015-600
Network Components
Terminating Resistors
DeviceNet requires a terminating resistor to be installed at each end of the trunk.
The following are the requirements for resistors:
•
121 ohm.
•
1% Metal Film.
•
0.25 Watt.
Connectors
All connectors must support five conductors, which consists of a signal pair, power
pair, and a drain wire. For more information on the Open Connector Pinout, refer to
.
It is recommended that the connector should be keyed such that a DeviceNet cable
exits the instrument or device without interfering with any indicators, auxiliary
connectors, or other devices that require access in the field. The DeviceNet
receptacle on the device should be mounted such that the key orientation allows the
cable to have no interference with indicators, auxiliary connectors, or other devices
that may require access in the field.
Hard-wired connections such as direct soldering, crimping, screw terminal blocks,
and barrier strips are allowed. These methods must support node removal without
trunk severing requirement.
The following are the minimum requirements for a DeviceNet connector:
•
All wiping contacts must be gold plated.
•
A minimal operating voltage of 25 V.
•
A nominal contact resistance of less than 1 milliohm and should not exceed
5 milliohm over life.
Terminating resistors should be connected at both the ends of a trunk line.
Connecting the terminating resistor in the middle of a trunk line leads to improper
resistance and network failure.
Terminating resistors should not be connected at the end of a drop line.