Product Guide

1MRS758725

SSC600 
Product version: 1.0

4

ABB

earth faults close to the neutral earthing point of the transformer. 
Either the conventional high-impedance scheme or a numerical 
low-impedance scheme can be selected for protection of the 
transformer windings. When low-impedance restricted earth-
fault protection is used neither stabilizing resistors nor varistors 

are needed and as a further benefit the transforming ratio of the 

neutral earthing CTs can differ from those of the phase current 
transformers. Due to its unit protection character and absolute 
selectivity restricted earth fault does not need to be timegraded
with other protection schemes, and therefore high speed fault 
clearance can be achieved. The device also incorporates a ther-
mal overload protection function, which supervises the thermal 
stress of the transformer windings to prevent premature aging 
of the insulation of the windings. Multiple stages of short circuit, 
phase overcurrent, negative-sequence and earth-fault backup 
protection are separately available for both sides of the power 
transformer. Earth-fault protection based on the measured or cal-
culated residual voltage is also available. Further, the device also 
offers circuit breaker failure protection.

The device offers all the functionality needed to manage motor 
start-ups and normal operation, also including protection and fault 
clearance in abnormal situations. The main features of the device 
include thermal overload protection, motor start-up supervision,
locked rotor protection and protection against too frequent motor 
start-ups. The device also incorporates nondirectional earth-fault 
protection, negative phase-sequence current unbalance protec-
tion and backup overcurrent protection. Furthermore, the device 
offers motor running stall protection, loss-of-load supervision and 
phase reversal protection. In certain motor drives of special im-
portance there must be a possibility to override the motor thermal 
overload protection to perform an emergency start of a hot motor. 
To enable an emergency hot start, the SSC600 offers a forced 
start execution feature.

Some product options additionally offer multifrequency admit-
tance-based earth-fault protection providing selective directional 
earth-fault protection for high-impedance earthed networks. The 
operation is based on multifrequency neutral admittance measure-
ment utilizing fundamental frequency and harmonic components 

in Uo and Io. A special filtering algorithm enables dependable and 

secure fault direction also during intermittent/restriking earth faults. 
It provides a very good combination of reliability and sensitivity of 
protection with a single function for low ohmic and higher ohmic 
earth faults and for transient and intermittent or restriking earth 
faults.

SSC600 also features optional arc fault protection of the circuit 
breaker, busbar and cable compartment of metal-enclosed indoor 
switchgear. Light detection needs to be included in the bay level 
devices.

3. Supported ABB Solutions

The SSC600 Smart Substation devices together with the Substa-
tion Management Unit COM600S constitute a genuine IEC 61850 
solution for reliable power distribution in utility and industrial power 
systems. To facilitate the system engineering, ABB’s devices are
supplied with connectivity packages. The connectivity packages 

include a compilation of software and device-specific information, 

including single-line diagram templates and a full device data 
model. The data model includes event and parameter lists. With 

the connectivity packages, the devices can be readily configured 

using PCM600 and integrated with COM600S or the network 
control and management system MicroSCADA Pro.

The SSC600 Smart Substation devices offer native support for 
IEC 61850 Edition 2 also including binary and analog horizontal 
GOOSE messaging. In addition, with process bus the receiving of 
sampled values of voltages is supported. Compared to traditional 
hardwired, inter-device signaling, peer-to-peer communication 
over a switched Ethernet LAN offers an advanced and versatile 
platform for power system protection. Among the distinctive 
features of the protection system approach, enabled by the full 
implementation of the IEC 61850 substation automation standard, 
are fast communication capability, continuous supervision of the 
protection and communication system’s integrity, and an inherent 

flexibility regarding reconfiguration and upgrades.This protection 

device series is able to optimally utilize interoperability provided by 
the IEC 61850 Edition 2 features.

At substation level, COM600S uses the data content of the 
devices to enhance substation level functionality. COM600S 
features a Web browser-based HMI, which provides a customiz-
able graphical display for visualizing single-line mimic diagrams for 
switchgear bay solutions. Substation devices and processes can 
also be remotely accessed through the Web HMI, which improves 
personnel safety.

In addition, COM600S can be used as a local data warehouse for 
the substation’s technical documentation and for the network data 
collected by the devices. The collected network data facilitates 
extensive reporting and analyzing of network fault situations by
using the data historian and event handling features of COM600S. 
The historical data can be used for accurate monitoring of process 
and equipment performance, using calculations based on both 
real-time and historical values. A better understanding of the
process dynamics is achieved by combining time-based process 
measurements with production and maintenance events.

Содержание ABILITY SSC600

Страница 1: ...ABB ABILITY SMART SUBSTATION CONTROL AND PROTECTION FOR ELECTRICAL SYSTEMS JANUARY 2019 PRODUCT GUIDE SSC600...

Страница 2: ...a commitment by ABB ABB assumes no responsibility for any errors that may appear in this document Copyright 2019 ABB All rights reserved Trademarks ABB and Relion are registered trademarks of the ABB...

Страница 3: ...a tor transformer blocks in utility and industry power distribution systems Once the device has been given the application specific settings it can directly be put into service 2 Protection functions...

Страница 4: ...w ohmic and higher ohmic earth faults and for transient and intermittent or restriking earth faults SSC600 also features optional arc fault protection of the circuit breaker busbar and cable compartme...

Страница 5: ...rrent and residual voltage based on the received process bus measurements The residual voltage The phase voltages The voltage sequence components Frequency The device also calculates the demand value...

Страница 6: ...me stamps The non volatile memory retains its data even if the device temporarily loses its auxiliary supply The event log facilitates detailed pre and post fault analyses of feeder faults and disturb...

Страница 7: ...e supports simultaneous event reporting to five different clients on the station bus The device can exchange data with other devices using the IEC 61850 protocol The device can send binary and analog...

Страница 8: ...supports the following high accuracy time synchro nization method with a timestamping resolution of 4 s required especially in process bus applications PTP IEEE 1588 v2 with Power Profile IEEE 1588 v...

Страница 9: ...ns Description Value Operating temperature range 20 55 C continuous Short time Short time service temperature range 25 70 C 16h 1 2 Relative humidity 95 non condensing Atmospheric pressure Altitude Tr...

Страница 10: ...ard Vibration response and endurance test 6 10 1 Class 1 IEC 60255 21 1 Shock response test 6 10 2 Class 1 IEC 60255 21 2 Shock endurance test 6 10 2 Class 1 IEC 60255 21 2 Bumb test 6 10 2 Class 1 IE...

Страница 11: ...PTOC 40 200000 ms 10 Operating curve type 6 PHLPTOC Definite or inverse time Curve type 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 17 18 19 PHHPTOC Definite or inverse time Curve type 1 3 5 9 10 12 15 17 PHI...

Страница 12: ...1 10 In 5 0 of the set value at currents in the range of 10 40 In Start time 11 12 EFIPTOC IFault 2 set Start value IFault 10 set Start value Minimum Typical Maximum 16 ms 11 ms 19 ms 12 ms 23 ms 14...

Страница 13: ...ange Step Start value DEFLPDEF 0 010 5 000 In 0 005 DEFHPDEF 0 10 40 00 In 0 01 Directional mode DEFLPDEF and DEFHPDEF 1 Non directional 2 Forward 3 Reverse Time multiplier DEFLPDEF 0 05 15 00 0 01 DE...

Страница 14: ...metric based earth fault protection WPWDE Characteristic Value Operation accuracy Current and voltage 1 5 of the set value or 0 002 In Power 3 of the set value or 0 002 Pn Start time 2526 Typically 63...

Страница 15: ...20 ms Reset time Typically 40 ms Reset ratio Typically 0 96 Retardation time 35 ms Operate time accuracy in definite time mode 1 0 of the set value or 20 ms Operate time accuracy in inverse time mode...

Страница 16: ...Minimum Typical Maximum 62 ms 66 ms 70 ms Reset time Typically 40 ms Reset ratio Depends on the set Relative hysteresis Retardation time 35 ms Operate time accuracy in definite time mode 1 0 of the s...

Страница 17: ...5 ms Operate time accuracy in definite time mode 1 0 of the set value or 20 ms Suppression of harmonics DFT 50 dB at f n fn where n 2 3 4 5 Table 37 Positive sequence undervoltage protection PSPTUV ma...

Страница 18: ...of the set value or 30 ms Table 41 Frequency protection FRPFRQ main settings Parameter Function Value Range Step Operation mode FRPFRQ 1 Freq 2 Freq 3 df dt 4 Freq df dt 5 Freq df dt 6 Freq OR df dt 7...

Страница 19: ...TTR 0 05 4 00 In 0 01 Temperature rise T1PTTR 0 0 200 0 C 0 1 Time constant T1PTTR 60 60000 s 1 Maximum temperature T1PTTR 20 0 200 0 C 0 1 Alarm value T1PTTR 20 0 150 0 C 0 1 Reclose temperature T1PT...

Страница 20: ...tection ARCSARC Characteristic Value Operation accuracy 3 of the set value or 0 01 In Operate time Operation mode Light current 45 46 Minimum Typical Maximum 9 ms 47 4 ms 48 12 ms 47 6 ms 48 15 ms 47...

Страница 21: ...based earth fault protection MFADPSDE Characteristic Value Operation accuracy 1 0 of the set value or 20 ms 1 5 of the set value or 0 002 Un Start time56 Typically 35 ms Reset time Typically 40 ms Ope...

Страница 22: ...racteristic Value Operation accuracy Depending on the frequency of the measured current fn 2 Hz 1 5 of the set value or 0 002 In Start time Typically 300 ms Reset time Typically 40 ms Reset ratio Typi...

Страница 23: ...stall 4 IIt stall CB Restart inhibit time STTPMSU 0 250 min 1 Table 68 Phase reversal protection PREVPTOC Characteristic Value Operation accuracy Depending on the frequency of the measured current fn...

Страница 24: ...0 002 x In at currents in the range of 0 01 4 00 x In Operate time accuracy 57 2 0 of the theoretical value or 0 50 s Table 73 Three phase thermal overload protection two time constants T2PTTR main s...

Страница 25: ...impedance restricted earth fault protection LREFPNDF Characteristic Value Operation accuracy Depending on the frequency of the measured current fn 2 Hz 2 5 of the set value or 0 002 x In Start time 60...

Страница 26: ...racy Depending on the frequency of the measured current and voltage fn 2 Hz Reactive power range PF 0 71 Power 3 0 or 0 002 Qn Voltage 1 5 of the set value or 0 002 Un Start time 62 63 Typically 46 ms...

Страница 27: ...VRTPTUV 0 00 1 20 ms 0 01 Voltage level 5 LVRTPTUV 0 00 1 20 ms 0 01 Voltage level 6 LVRTPTUV 0 00 1 20 ms 0 01 Voltage level 7 LVRTPTUV 0 00 1 20 ms 0 01 Voltage level 8 LVRTPTUV 0 00 1 20 ms 0 01 Vo...

Страница 28: ...ain settings Parameter Function Value Range Step Live dead mode SECRSYN 1 Off 1 Both Dead 2 Live L Dead B 3 Dead L Live B 4 Dead Bus L Any 5 Dead L Bus Any 6 One Live Dead 7 Not Both Live Difference v...

Страница 29: ...measurement CSMSQI Characteristic Value Operation accuracy Depending on the frequency of the measured current f fn 2 Hz 1 0 or 0 002 In at currents in the range of 0 01 4 00 In Suppression of harmonic...

Страница 30: ...e voltages in range 0 50 1 15 Un At the frequency fn 1 Hz 1 5 for apparent power S 1 5 for active power P and active energy 67 1 5 for reactive power Q and reactive energy 68 0 015 for power factor Su...

Страница 31: ...splay offer front panel user interface functionality with menu navigation and menu views In addition WHMI includes a user configurable single line diagram SLD with position indication for the associat...

Страница 32: ...ser Internet Explorer 8 0 9 0 10 0 and 11 0 SSC600 Connectivity Package 1 0 or later Table 102 Supported functions Function Web HMI PCM600 Device parameter setting Saving of device parameter settings...

Страница 33: ...earth fault protection high stage DEFHPDEF1 Io 1 67N 2 1 Admittance based earth fault protection EFPADM1 Yo 1 21YN 1 Wattmetric based earth fault protection WPWDE1 Po 1 32N 1 Transient intermittent ea...

Страница 34: ...60617 IEC ANSI Current total demand distortion CMHAI1 PQM3I 1 PQM3I 1 Voltage total harmonic distortion VMHAI1 PQM3U 1 PQM3V 1 Voltage variation PHQVVR1 PQMU 1 PQMV 1 Voltage unbalance VSQVUB1 PQUUB 1...

Страница 35: ...1 SCA4 1 SCA4 1 Integer value move MVI4GAPC1 MVI4 1 MVI4 1 28 Order form Table 110 Order code example Order code digits 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 S B A C A N A N A A A 1 A N N 1 1G Tab...

Страница 36: ...nits relays A Communica tion A 9 or A Z A B No additional communication cards Ethernet 1000Base SX 2 x LC with PRP A Communica tion protocol A 9 or A Z A IEC 61850 A Language 1 9 1 English 1 Table 113...

Страница 37: ...l overvoltage protection ROVPTOV 8 Three phase undervoltage protection for 10 feeders across 4 bus sections PHPTUV 40 Three phase overvoltage protection for 10 feeders across 4 bus sections PHPTOV 8 P...

Страница 38: ...0 Name Number of Instances OR gate with two inputs OR2 800 OR gate with six inputs OR6 400 OR gate with twenty inputs OR20 200 AND gate with two inputs AND2 800 AND gate with six inputs AND6 400 AND g...

Страница 39: ...information GOOSERCV_ENUM 200 29 2 Feeder Application Package Feeder Application Package can be selected with order code Digit 4 and it can be selected for 5 10 15 or 20 feeders The size of the packa...

Страница 40: ...ault locator SCEFRFLO 5 10 15 20 Directional reactive power under voltage protection DQPTUV 5 10 15 20 Low voltage ride through protection LVRTPTUV 15 30 45 60 29 4 Transformer Application Package Tra...

Страница 41: ...TTPMSU 5 10 15 20 Phase reversal protection PREVPTOC 5 10 15 20 Thermal overload protection for motors MPTTR 5 10 15 20 29 6 Special Application Package Special optional applications can be selected w...

Страница 42: ...reserved Specifications subject to change without notice Document ID 1MRS758725 ABB Distribution Solutions Distribution Automation P O Box 699 FI 65101 VAASA Finland Phone 358 10 22 11 Fax 358 10 22 4...