TITLETEXTFRAME
25
ABB
Product Guide
1MRS758725
SSC600
Product version: 1.0
Table 75. Stabilized and instantaneous differential protection for two-winding transformers (TR2PTDF) main settings
Parameter
Function
Value (Range)
Step
High operate value
TR2PTDF
500...3000 %Ir
10
Low operate value
TR2PTDF
5...50 %Ir
1
Slope section 2
TR2PTDF
10...50%
1
End section 2
TR2PTDF
100...500 %Ir
1
Restraint mode
TR2PTDF
5 = Waveform
6 = 2.h + waveform
8 = 5.h + waveform
9 = 2.h + 5.h + wav
-
Start value 2.H
TR2PTDF
7...20%
1
Start value 5.H
TR2PTDF
10...50%
1
Operation
TR2PTDF
1 = on
5 = off
-
Winding 1 type
TR2PTDF
1 = Y
2 = YN
3 = D
4 = Z
5 = ZN
-
Winding 2 type
TR2PTDF
1 = Y
2 = YN
3 = D
4 = Z
5 = ZN
-
Zro A elimination
TR2PTDF
1 = Not eliminated
2 = Winding 1
3 = Winding 2
4 = Winding 1 and 2
-
Table 76. Numerically stabilized low-impedance restricted earth-fault protection (LREFPNDF)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: fn ±2 Hz
±2.5% of the set value or ±0.002 x In
Start time
60, 61
IFault = 2.0 × set Operate value
Minimum
Typical
Maximum
37 ms
41 ms
45 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5, …
Table 77. Stabilized restricted earth-fault protection (LREFPNDF) main settings
Parameter
Function
Value (Range)
Step
Operate value
LREFPNDF
5...50 %In
1
Minimum operate time
LREFPNDF
40...300000 ms
1
Restraint mode
LREFPNDF
1 = None
2 = Harmonic
-
Start value 2.H
LREFPNDF
10...50%
1
Operation
LREFPNDF
1 = on
5 = off
-
60 Current before fault = 0.0, fn = 50 Hz, results based on statistical distribution of 1000 measurements
61 Includes the delay of the signal output contact