TITLETEXTFRAME
27
ABB
Product Guide
1MRS758725
SSC600
Product version: 1.0
Table 81. Low-voltage ride-through protection (LVRTPTUV)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
voltage: fn ±2 Hz
±1.5% of the set value or ±0.002 × Un
Start time
64, 65
Typically 40 ms
Reset time
Based on maximum value of Recovery time setting
Operate time accuracy
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
Table 82. Low-voltage ride-through protection (LVRTPTUV) main settings
Parameter
Function
Value (Range)
Step
Voltage start value
LVRTPTUV
0.05...1.20 × Un
0.01
Num of start phases LVRTPTUV
4 = Exactly 1 of 3
5 = Exactly 2 of 3
6 = Exactly 3 of 3"
-
Voltage selection
LVRTPTUV
1 = Highest Ph-to-E
2 = Lowest Ph-to-E
3 = Highest Ph-to-Ph
4 = Lowest Ph-to-Ph
5 = Positive Seq
-
Active coordinates
LVRTPTUV
1...10
1
Voltage level 1
LVRTPTUV
0.00...1.20 ms
0.01
Voltage level 2
LVRTPTUV
0.00...1.20 ms
0.01
Voltage level 3
LVRTPTUV
0.00...1.20 ms
0.01
Voltage level 4
LVRTPTUV
0.00...1.20 ms
0.01
Voltage level 5
LVRTPTUV
0.00...1.20 ms
0.01
Voltage level 6
LVRTPTUV
0.00...1.20 ms
0.01
Voltage level 7
LVRTPTUV
0.00...1.20 ms
0.01
Voltage level 8
LVRTPTUV
0.00...1.20 ms
0.01
Voltage level 9
LVRTPTUV
0.00...1.20 ms
0.01
Voltage level 10
LVRTPTUV
0.00...1.20 ms
0.01
Recovery time 1
LVRTPTUV
0...300000 ms
1
Recovery time 2
LVRTPTUV
0...300000 ms
1
Recovery time 3
LVRTPTUV
0...300000 ms
1
Recovery time 4
LVRTPTUV
0...300000 ms
1
Recovery time 5
LVRTPTUV
0...300000 ms
1
Recovery time 6
LVRTPTUV
0...300000 ms
1
Recovery time 7
LVRTPTUV
0...300000 ms
1
Recovery time 8
LVRTPTUV
0...300000 ms
1
Recovery time 9
LVRTPTUV
0...300000 ms
1
Recovery time 10
LVRTPTUV
0...300000 ms
1
17. Power quality functions
Table 83. Voltage variation (PHQVVR)
Characteristic
Value
Operation accuracy
±1.5% of the set value or ±0.2% of reference voltage
Reset ratio
Typically 0.96 (Swell), 1.04 (Dip, Interruption)
Table 84. Voltage unbalance (VSQVUB)
Characteristic
Value
Operation accuracy
±1.5% of the set value or ±0.002 × Un
Reset ratio
Typically 0.96
64 Tested for Number of Start phases = 1 out of 3, results based on statistical distribution of 1000 measurements
65 Includes the delay of the signal output contact