13
ABB
Product Guide
1MRS758725
SSC600
Product version: 1.0
Parameter
Function
Value (Range)
Step
Operating curve type
14
EFLPTOC
Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19
EFHPTOC
Definite or inverse time
Curve type: 1, 3, 5, 9, 10, 12, 15, 17
EFIPTOC
Definite time
Table 18. Directional earth-fault protection (DEFxPDEF
Characteristic
Value
Operation accuracy
EFLPTOC
Depending on the frequency of the measured current: fn ±2 Hz
±1.5% of the set value or ±0.002 × In
EFHPTOC and
EFIPTOC
±1.5% of set value or ±0.002 × In (at currents in the range of 0.1…10 × In)
±5.0% of the set value (at currents in the range of 10…40 × In)
Start time
15, 16
EFIPTOC:
IFault = 2 × set Start value
IFault = 10 × set Start value
Minimum
Typical
Maximum
16 ms
11 ms
19 ms
12 ms
23 ms
14 ms
EFHPTOC and EFLPTOC:
IFault = 2 × set Start value
23 ms
26 ms
29 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<30 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±1.0% of the set value or ±20 ms
17
Suppression of harmonics
RMS: No suppression
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression
Table 19. Directional earth-fault protection (DEFxPDEF) main settings
Parameter
Function
Value (Range)
Step
Start value
DEFLPDEF
0.010...5.000 × In
0.005
DEFHPDEF
0.10...40.00 × In
0.01
Directional mode
DEFLPDEF and
DEFHPDEF
1 = Non-directional
2 = Forward
3 = Reverse
-
Time multiplier
DEFLPDEF
0.05...15.00
0.01
DEFHPDEF
0.05...15.00
0.01
Operate delay time
DEFLPDEF
50...200000 ms
10
DEFHPDEF
40...200000 ms
10
Operating curve type
18
DEFLPDEF
Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19
DEFHPDEF
Definite or inverse time
Curve type: 1, 3, 5, 15, 17
Operation mode
DEFxPDEF
1 = Phase angle
2 = IoSin
3 = IoCos
4 = Phase angle 80
5 = Phase angle 88
-
Table 20. Admittance-based earth-fault protection (EFPADM)
Characteristic
Value
Operation accuracy
19
At the frequency f = fn
±1.0% or ±0.01 mS (In range of 0.5...100 mS)
Start time
20
Minimum
Typical
Maximum
56 ms
60 ms
64 ms
Reset time
40 ms
14 For further reference, see the Operation characteristics table
15 Measurement mode = default (depends on stage), current before fault = 0.0 × In, fn = 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based
on statistical distribution of 1000 measurements
16 Includes the delay of the signal output contact
17 Maximum Start value = 2.5 × In, Start value multiples in range of 1.5...20
18 For further reference, see the Operating characteristics table
19 Uo = 1.0 × Un
20 Includes the delay of the signal output contact, results based on statistical distribution of 1000 measurements Feeder Protection and Control 1MRS756379 S REF615 Product version:
5.0 FP1 52