Appendix A Error Messages
3BSE037076-510 D
101
FILE_FORMAT
File format error in Remote Access Client service data.
This may happen if a newer version of the Multisystem
Integration function is installed and will require a full new
upload to get correct data.
FILE_VERSION
File version error in Remote Access Client service data.
This may happen if a newer version of the Multisystem
Integration function is installed and will require a full new
upload to get correct data.
HDA_BAD_HANDLE
Internal error. History server encountered a bad
(unknown) handle.
HDA_BAD_ITEMID
Internal error. History server address with malformed item
identifier.
HDA_NOT_INITED
Internal error. History server linked adaptor not initialized
before use.
HDA_REFERENCE_NOT_FOUND
*
A referenced aspect in a history log configuration is not
found in the provider.
INITED
Internal error. Object is re-initialized after first use.
ID_USED
The user mapping is already used.
ID_IN_USE
Internal error. Identifier already in use.
INVALID_SECTION
*
A section is uploaded through a reference without being
explicitly uploaded. Upload the section before any objects
referencing the section.
MANAGED_READONLY
Internal error. A read-only property table was the target
for an update.
NODE_ADMIN_ERROR
*
Internal error. Handling of the pseudo nodes representing
the remote system failed.
NO_CONNECTION
Currently no connection open to the provider system.
Check the connection status to pinpoint the problem.
Table 8. 800xA Multisystem Integration Error Messages (Continued)
Error Messages
Description
Содержание Ability 800xA Series
Страница 1: ...Power and productivity for a better world T System 800xA Multisystem Integration System Version 5 1...
Страница 2: ......
Страница 3: ...System 800xA Multisystem Integration System Version 5 1...
Страница 18: ...Prerequisites and Requirements Section 1 Introduction 18 3BSE037076 510 D...
Страница 26: ...Medium Large Configuration Section 2 Installation 26 3BSE037076 510 D...
Страница 74: ...Limitations Section 3 Configuration 74 3BSE037076 510 D...
Страница 98: ...Upgrade Procedure Section 5 Maintenance 98 3BSE037076 510 D...
Страница 106: ...Appendix A Error Messages 106 3BSE037076 510 D...
Страница 112: ...No System Alarm in the Provider System Appendix B Fault Tracing 112 3BSE037076 510 D...
Страница 116: ...Index 116 3BSE037076 510 D Index 116 3BSE037076 510 D...
Страница 120: ...Updates in Revision Index D 120 3BSE037076 510 D...
Страница 121: ......