Appendix B Fault Tracing
No Alarm and Event in the Subscriber System
3BSE037076-510 D
109
No Alarm and Event in the Subscriber System
If there are no Alarm and Event from the provider system in the subscriber, check
the following:
1.
Is the connection to the provider up and running?
2.
Is the object generating the alarm uploaded to the subscriber system? If not,
make sure to upload it, because alarms from objects not uploaded will not be
shown in the alarm list.
3.
Check the service providers for the Alarm Manager, and Event Collector in the
Service structure on the subscriber node. Are they all working correct?
4.
Check the service providers for the Alarm Manager and Event Collector in the
Service structure on the provider node. Are they all working correct?
Alarm with Object GUID Instead of Object Name
Alarms from objects that has been uploaded, but later not uploaded will be
presented as object GUID instead of the object name. To correct this the Remote
System object representing the provider has to be deleted and a new configuration
and upload to be executed.
Failed to Deploy Graphic Display
If a graphic display is failing when doing deploy (finalize) check the following
things:
1.
Is it possible to deploy the graphic display in the provider?
2.
Are all referenced graphic elements uploaded?
3.
If the graphic display contains composite display elements, are they explicitly
uploaded to the control structure?
4.
Does the display or display element contain user written Visual Basic code that
requires a specific environment to work.
No System Alarm in the Provider System
If there is no System Alarm when the connection to the provider system is broken,
check the following to configure the System Alarm:
Содержание Ability 800xA Series
Страница 1: ...Power and productivity for a better world T System 800xA Multisystem Integration System Version 5 1...
Страница 2: ......
Страница 3: ...System 800xA Multisystem Integration System Version 5 1...
Страница 18: ...Prerequisites and Requirements Section 1 Introduction 18 3BSE037076 510 D...
Страница 26: ...Medium Large Configuration Section 2 Installation 26 3BSE037076 510 D...
Страница 74: ...Limitations Section 3 Configuration 74 3BSE037076 510 D...
Страница 98: ...Upgrade Procedure Section 5 Maintenance 98 3BSE037076 510 D...
Страница 106: ...Appendix A Error Messages 106 3BSE037076 510 D...
Страница 112: ...No System Alarm in the Provider System Appendix B Fault Tracing 112 3BSE037076 510 D...
Страница 116: ...Index 116 3BSE037076 510 D Index 116 3BSE037076 510 D...
Страница 120: ...Updates in Revision Index D 120 3BSE037076 510 D...
Страница 121: ......