6.5 Type PROFINET Internal Device
6.5.1 Input Size
Parent
Input Size
belongs to the type
PROFINET Internal Device
, in the topic
I/O System
.
Cfg name
InputSize
Description
The parameter
Input Size
is used to configure the input slot configuration of the
PROFINET internal device.
Usage
It will configure the input slot size for the PROFINET internal device. This size must
match the connecting PLC’s or other PROFINET controller’s defined output slot
size. For more information, see
Input and output size on page 30
.
Prerequisites
The option
PROFINET Controller/Device
or
PROFINET Device
must be installed.
Default value
The default value is 64 bytes (512 signal bits).
Allowed values
8, 16, 32, 64, 128 or 256 bytes (64, 128, 512, 1024 or 2048 signal bits).
Application manual - PROFINET Controller/Device
67
3HAC050969-001 Revision: G
© Copyright 2015-2018 ABB. All rights reserved.
6 System parameters
6.5.1 Input Size