1MAC052634-MB D
Section 4
Modbus parameters and diagnostics
615/620 series ANSI
49
Communication Protocol Manual
4.2
Monitored data
The Modbus serial monitored data can be accessed with PST or via the LHMI path
Monitoring > Communication > Modbus > Serial
.
Table 36:
Modbus serial
The Modbus Ethernet monitored data can be accessed with PST or via the LHMI path
Monitoring > Communication > Modbus > Ethernet
.
Table 37:
Modbus TCP/IP
Parameter
Values (range)
Description
Received frames N
1
1. N = instance number 1, 2...
0...2147483648
Received Modbus frames by instance N
Transmitted frames N
0...2147483648
Transmitted Modbus frames by instance N
Cksm Err N
0...2147483648
Checksum errors detected by instance N
Transmitted Exec A N
0...2147483648
Transmitted exception responses 1 and 2 by instance N
Transmitted Exec B N
0...2147483648
Transmitted exception responses 3 by instance N
Status N
True, False
Status of communication, instance N
Reset of diagnostic counters instance N
Parameter
Values (range)
Description
Received frames N
1
1. N = instance number 1, 2...
0...2147483648
Received Modbus frames by instance N
Transmitted frames N
0...2147483648
Transmitted Modbus frames by instance N
Transmitted Exec A N
0...2147483648
Transmitted exception responses 1 and 2 by instance N
Transmitted Exec B N
0...2147483648
Transmitted exception responses 3 by instance N.
Cn Rejects No socket
0...2147483648
Connection rejections due to no free sockets
Cn Rejects Not reg
0...2147483648
Connection rejections due to not registered client IP.
Status N
True, False
Status of communication, instance N
Reset of diagnostic counters instance N