Section 3
1MAC052634-MB D
Vendor-specific implementation
34
615/620 series ANSI
Communication Protocol Manual
Table 22:
Modbus event value alternatives
Table 23:
Interpretation of the one-bit data value
Table 24:
Interpretation of the two-bit data value
Object derived from
IEC 61850 Class
Meaning
One Bit Data
Value
Two Bit Data
Value
32 bit Data
Value
SPS
Single Point Status
X
SPC
Single Point Status of a controllable
object
X
DPS
Dual Point Status
X
DPC
Dual Point Status of a controllable
object
X
ACT
Trip status
X
ACD
Start/Pick-up status
X
INS/INC
Integer status
X
Register 4xxxx binary coded value
Meaning
xxxx.xxxx.xxxx.xxx0
Object in OFF position
xxxx.xxxx.xxxx.xxx1
Object in ON position
Register 4xxxx binary coded value
Meaning
xxxx.xxxx.xxxx.xx00
Object in intermediate position (changing)
xxxx.xxxx.xxxx.xx01
Object in ON (close) position
xxxx.xxxx.xxxx.xx10
Object in OFF (open) position
xxxx.xxxx.xxxx.xx11
Object in faulty position
In case of a DPS/DPC two-bit event value (Data value identification = 2),
the data object ID registers always refer to the Modbus address or UID of
the CLOSE momentary value bit.