1MAC052634-MB D
Section 4
Modbus parameters and diagnostics
615/620 series ANSI
47
Communication Protocol Manual
Section 4
Modbus parameters and diagnostics
4.1
Parameter list
The Modbus parameters can be accessed with PCM600 or via the LHMI path
Configuration > Communication > Modbus
.
Table 35:
MODBUS settings
Parameter
Values (Range)
Unit
Step
Default
Description
InOv
0=False
1=True
0=False
Modbus Internal
Overflow:
TRUE-System level
overflow occurred
(indication only)
Serial port 1
0=Not in use
1=COM 1
2=COM 2
0=Not in use
COM port for Serial
interface 1
Parity 1
0=none
1=odd
2=even
2=even
Parity for Serial
interface 1
Address 1
1...255
1
Modbus unit address
on Serial interface 1
Link mode 1
1=RTU
2=ASCII
1=RTU
Modbus link mode
on Serial interface 1
Start delay 1
0...20
char
4
Start frame delay in
chars on Serial
interface 1
End delay 1
0...20
char
3
End frame delay in
chars on Serial
interface 1
Serial port 2
0=Not in use
1=COM 1
2=COM 2
0=Not in use
COM port for Serial
interface 2
Parity 2
0=none
1=odd
2=even
2=even
Parity for Serial
interface 2
Address 2
1...255
2
Modbus unit address
on Serial interface 2
Link mode 2
1=RTU
2=ASCII
1=RTU
Modbus link mode
on Serial interface 2
Start delay 2
0...20
4
Start frame delay in
chars on Serial
interface 2
End delay 2
0...20
3
End frame delay in
chars on Serial
interface 2
MaxTCPClients
0...5
5
Maximum number of
Modbus TCP/IP
clients