Type CO Overcurrent Relay
41-101U
5
ENERGY REQUIREMENTS
TYPE CO-2 RELAY
VOLT AMPERES**
Continuous
One Second
Power
At
At 3 Times
At 10 Times
At 20 Times
Ampere
Rating
Rating*
Factor
Tap Value
Tap Value
Tap Value
Tap Value
Range
Tap
(Amperes)
(Amperes)
Angle
ø
Current
Current
Current
Current
0.5
0.91
28
58
4.8
39.6
256
790
0.6
0.96
28
57
4.9
39.8
270
851
0.8
1.18
28
53
5.0
42.7
308
1024
0.5/2.5
1.0
1.37
28
50
5.3
45.4
348
1220
1.5
1.95
28
40
6.2
54.4
435
1740
2.0
2.24
28
36
7.2
65.4
580
2280
2.5
2.50
28
29
7.9
73.6
700
2850
2.0
3.1
110
59
5.04
38.7
262
800
2.5
4.0
110
55
5.13
39.8
280
920
3.0
4.4
110
51
5.37
42.8
312
1008
2/6
3.5
4.8
110
47
5.53
44.3
337
1120
4.0
5.2
110
45
5.72
46.0
360
1256
5.0
5.6
110
41
5.90
50.3
420
1500
6.0
6.0
110
37
6.54
54.9
474
1800
4.0
7.3
230
64
4.92
39.1
268
848
5.0
8.0
230
50
5.20
42.0
305
1020
6.0
8.8
230
47
5.34
44.1
330
1128
4/12
7.0
9.6
230
46
5.53
45.8
364
1260
8.0
10.4
230
43
5.86
49.9
400
1408
10.0
11.2
230
37
6.60
55.5
470
1720
12.0
12.0
230
34
7.00
62.3
528
2064
VOLT AMPERES**
Continuous
One Second
Power
At
At 3 Times
At 10 Times
At 20 Times
Ampere
Rating
Rating*
Factor
Tap Value
Tap Value
Tap Value
Tap Value
Range
Tap
(Amperes)
(Amperes)
Angle
ø
Current
Current
Current
Current
0.5
2.7
88
69
3.92
20.6
103
270
0.6
3.1
88
68
3.96
20.7
106
288
0.8
3.7
88
67
4.01
21.0
120
325
0.5/2.5
1.0
4.1
88
66
4.07
22.3
130
400
1.5
5.7
88
62
4.19
23.2
147
462
2.0
6.8
88
60
4.30
24.9
168
548
2.5
7.7
88
58
4.37
26.2
180
630
2
8.0
230
67
3.88
21.0
110
308
2.5
8.8
230
66
3.90
21.6
118
342
3
9.7
230
64
3.93
22.1
126
381
2/6
3.5
10.4
230
63
4.09
23.1
136
417
4
11.2
230
62
4.12
23.5
144
448
5
12.5
230
59
4.20
24.8
162
540
6
13.7
230
57
4.38
26.5
183
624
4
16.0
460
65
4.00
22.4
126
376
5
18.8
460
63
4.15
23.7
143
450
6
19.3
460
61
4.32
25.3
162
531
4/12
7
20.8
460
59
4.35
26.4
183
611
8
22.5
460
56
4.40
27.8
204
699
10
25.0
460
53
4.60
30.1
247
880
12
28.0
460
47
4.92
35.6
288
1056
*
Thermal capacities for short times other than one second may be calculated on the basis of time being inversely proportional to the square of the current.
ø
Degrees current lags voltage at tap value current.
**
Voltages taken with Rectox type voltmeter.
CO-5 LONG TIME AND CO-6 DEFINITE MINIMUM TIME RELAYS
Содержание 41-101U
Страница 1: ......
Страница 8: ...41 101U Type CO Overcurrent Relay 8 Figure 7 Typical Time Curves of the Type CO 2 Relay Sub 1 619584 ...
Страница 9: ...Type CO Overcurrent Relay 41 101U 9 Figure 8 Typical Time Curves of the Type CO 5 Relay Sub 2 418245 ...
Страница 10: ...41 101U Type CO Overcurrent Relay 10 Figure 9 Typical Time Curves of the Type CO 6 Relay Sub 2 418246 ...
Страница 12: ...41 101U Type CO Overcurrent Relay 12 Figure 11 Typical Time Curves of the Type CO 8 Relay Sub 2 418248 ...
Страница 13: ...Type CO Overcurrent Relay 41 101U 13 Figure 12 Typical Time Curves of the Type CO 9 Relay Sub 2 418249 ...
Страница 14: ...41 101U Type CO Overcurrent Relay 14 Figure 13 Typical Time Curves of the Type CO 11 Relay Sub 2 288B655 ...
Страница 21: ...Type CO Overcurrent Relay 41 101U 21 RESERVED FOR NOTES ...