background image

Type CO Overcurrent Relay

41-101U

19

the operating time. Adjust the permanent magnet
keeper until the operating time corresponds to the
value of Table 2.

For type CO-11 relay only, the 1.30 times tap value
operating time from the number 6 time dial position
is 53.5

  ±

5% seconds. It is important that the 1.30

times tap value current be maintained accurately.
The maintaining of this current accurately is neces-
sary because of the steepness of the slope of the
time-current characteristic (Figure 13). A slight vari-
ation 

±

1%, in the 1.3 times tap value current (includ-

ing measuring instrument deviation) will change the
timing tolerance to 

±

10% and the effect of different

taps can make the total variations appear to be

±

15%. If the operating time at 1.3 times tap value is

not within these limits, a minor adjustment of the
control spring will give the correct operating time
without any undue effect on the minimum pick-up of
the relay. The check is to be made after the 2 times
tap value adjustment has been completed.

Apply the indicated current per Table 2 for the elec-
tromagnet plug adjustment (e.g., CO-8, 20 times tap
value) and measure the operating time. Adjust the
proper plug until the operating time corresponds to
the value in Table 2. (Withdrawing the left hand plug,
front view, increases the operating time and with-
drawing the right hand plug, front view, decreases
the time.) In adjusting the plugs, one plug should be
screwed in completely and the other plug run in or
out until the proper operating time has been ob-
tained.

Recheck the permanent magnet adjustment. If the
operating time for this calibration point has changed,
readjust the permanent magnet and then recheck
the electromagnet plug adjustment.

6.2.4

Indicating Contactor Switch (ICS)

Close the main relay contacts and pass sufficient dc
current through the trip circuit to close the contacts
of the ICS. This value of current should be not great-
er than the particular ICS tap setting being used. The
operation indicator target should drop freely.

6.2.5

Indicating Instantaneous Trip Unit (IIT)

The core screw must be adjusted to the value of
pick-up current desired.

The nameplate data will furnish the actual current
range that may be obtained from the IIT unit.

6.3

ROUTINE MAINTENANCE

All relays should be inspected and checked periodi-
cally to assure proper operation. Generally a visual
inspection should call attention to any noticeable
changes. A minimum suggested check on the relay
system is to close the contacts manually to assure
that the breaker trips and the target drops. Then re-
lease the contacts and observe that the reset is
smooth and positive.

If an additional time check is desired, pass second-
ary current through the relay and check the time of
operation. It is preferable to make this at several
times pick-up current at an expected operating point
for the particular application. For the .5 to 2.5 am-
pere range CO-5 and CO-6 induction unit use the al-
ternative test circuit in Figure 16 as these relays are
affected by a distorted wave form. With the connec-
tion the 25/5 ampere current transformers should be
worked well below the knee of the saturation (i.e.,
use 10L50 or better).

All contacts should be periodically cleaned. A con-
tact burnisher #182A836H01 is recommended for
this purpose. The use of abrasive material for clean-
ing contacts is not recommended, because of the
danger of embedding small particles in the face of
the soft silver and thus impairing the contact.

7.0

RENEWAL PARTS

Repair work can be done most satisfactorily at the
factory. However, interchangeable parts can be fur-
nished to the customers who are equipped for doing
repair work. When ordering parts, always give the
complete nameplate data.

Содержание 41-101U

Страница 1: ......

Страница 2: ...g Instantaneous Trip IIT 2 IIT Adjusting Screw 3 Indicating Contactor Switch ICS 4 Indicating Contactor Switch Tap Block Figure 2 Time Overcurrent Unit Front View 1 Tap block 2 Time Dial 3 Control Spring Assembly 4 Disc 5 Stationary Contact Assembly 6 Magnetic Plugs 7 Permanent Magnet ...

Страница 3: ...Type CO Overcurrent Relay 41 101U 3 Figure 3 E Type Electromagnet 1 Magnet Plugs 2 Tap Block 3 Tap Screw Figure 4 Indicating Instantaneous Trip Unit IIT Figure 5 Indicating Contactor Switch ICS ...

Страница 4: ...fluxes produced by the electromagnet result in out of phase fluxes in the air gap The out of phase air gap fluxes produced cause a contact closing torque 2 2 INDICATING CONTACTOR SWITCH UNIT ICS The dc indicating contactor switch is a small clapper type device A magnetic armature to which leaf spring mounted contacts are attached is attracted to the magnetic core upon energization of the switch Wh...

Страница 5: ...4 VOLT AMPERES Continuous One Second Power At At 3 Times At 10 Times At 20 Times Ampere Rating Rating Factor Tap Value Tap Value Tap Value Tap Value Range Tap Amperes Amperes Angle ø Current Current Current Current 0 5 2 7 88 69 3 92 20 6 103 270 0 6 3 1 88 68 3 96 20 7 106 288 0 8 3 7 88 67 4 01 21 0 120 325 0 5 2 5 1 0 4 1 88 66 4 07 22 3 130 400 1 5 5 7 88 62 4 19 23 2 147 462 2 0 6 8 88 60 4 3...

Страница 6: ...ONG TIME AND CO 9 DEFINITE MINIMUM TIME RELAYS VOLT AMPERES Continuous One Second Power At At 3 Times At 10 Times At 20 Times Ampere Rating Rating Factor Tap Value Tap Value Tap Value Tap Value Range Tap Amperes Amperes Angle ø Current Current Current Current 0 5 2 7 88 72 2 38 21 0 132 350 0 6 3 1 88 71 2 38 21 0 134 365 0 8 3 7 88 69 2 40 21 1 142 400 0 5 2 5 1 0 4 1 88 67 2 42 21 2 150 440 1 5 ...

Страница 7: ...0 2 0 7 0 230 32 0 73 6 30 74 0 264 2 5 7 8 230 30 0 78 7 00 78 5 285 3 0 8 3 230 27 0 83 7 74 84 0 309 2 6 3 5 9 0 230 24 0 88 8 20 89 0 340 4 0 10 0 230 23 0 96 9 12 102 0 372 5 0 11 0 230 20 1 07 9 80 109 0 430 6 0 12 0 230 20 1 23 11 34 129 0 504 4 0 14 0 460 29 0 79 7 08 78 4 296 5 0 16 0 460 25 0 89 8 00 90 0 340 6 0 17 0 460 22 1 02 9 18 101 4 378 4 12 7 0 18 0 460 20 1 10 10 00 110 0 454 8...

Страница 8: ...41 101U Type CO Overcurrent Relay 8 Figure 7 Typical Time Curves of the Type CO 2 Relay Sub 1 619584 ...

Страница 9: ...Type CO Overcurrent Relay 41 101U 9 Figure 8 Typical Time Curves of the Type CO 5 Relay Sub 2 418245 ...

Страница 10: ...41 101U Type CO Overcurrent Relay 10 Figure 9 Typical Time Curves of the Type CO 6 Relay Sub 2 418246 ...

Страница 11: ...Type CO Overcurrent Relay 41 101U 11 Sub 2 418247 Figure 10 Typical Time Curves of the Type CO 7 Relay Denotes Change ...

Страница 12: ...41 101U Type CO Overcurrent Relay 12 Figure 11 Typical Time Curves of the Type CO 8 Relay Sub 2 418248 ...

Страница 13: ...Type CO Overcurrent Relay 41 101U 13 Figure 12 Typical Time Curves of the Type CO 9 Relay Sub 2 418249 ...

Страница 14: ...41 101U Type CO Overcurrent Relay 14 Figure 13 Typical Time Curves of the Type CO 11 Relay Sub 2 288B655 ...

Страница 15: ...taps requires connecting the lead located in front of the tap block to the desired setting by means of a screw connection 3 2 TRIP CIRCUIT CONSTANTS Contactor Switch 0 2 ampere tap 6 5 ohms dc resistance 2 0 ampere tap 0 15 ohms dc resistance 4 0 SETTINGS CAUTION Since the tap block screw on both the CO unit and IIT unit carries operating current be sure that the screws are turned tight In order t...

Страница 16: ...tion of the 0 2 or 2 0 ampere setting This selection is made by connecting the lead located in front of the tap block to the desired setting by means of the connect ing screw 4 4 INDICATING INSTANTANEOUS TRIP IIT The IIT setting is the level of ac current at which it will pickup It should be set to coordinate with other de vices so it will never operate for a fault in protective zone where trippin...

Страница 17: ...ts normal deflection Therefore with the stationary contact resting against the backstop the index mark is offset to the right of the O mark by ap proximately 020 The placement of the various time dial positions in line with the index mark will give operating times as shown on the respective time current curves For double trip relays the fol low on the stationary contacts should be approximately 1 ...

Страница 18: ...old the armature closed against the core pin and gauge and adjust the stationary contacts such that they just make with the moving contact Both stationary con tacts should make at approximately the same time The contact follow will be approximately 1 64 to 3 64 6 2 CALIBRATION Use the following procedure for calibrating the relay if the relay has been taken apart for repairs or the ad justments di...

Страница 19: ...e the main relay contacts and pass sufficient dc current through the trip circuit to close the contacts of the ICS This value of current should be not great er than the particular ICS tap setting being used The operation indicator target should drop freely 6 2 5 Indicating Instantaneous Trip Unit IIT The core screw must be adjusted to the value of pick up current desired The nameplate data will fu...

Страница 20: ...RATING CURRENT OPERATING RELAY DIAL MULTIPLES OF TIME MULTIPLES OF TIME TYPE POSITION TAP VALUE SECONDS TAP VALUE SECONDS CO 2 6 3 0 57 20 0 22 CO 5 6 2 37 80 10 14 30 CO 6 6 2 2 46 20 1 19 CO 7 6 2 4 27 20 1 11 CO 8 6 2 13 35 20 1 11 CO 9 6 2 8 87 20 0 65 CO 11 6 2 11 27 20 0 24 For 50 Hertz CO 11 relay 20 times operating time limits are 0 24 10 5 ...

Страница 21: ...Type CO Overcurrent Relay 41 101U 21 RESERVED FOR NOTES ...

Страница 22: ...41 101U Type CO Overcurrent Relay 22 Denotes Change Figure 19 Outline and Drilling Plan for the Type CO Relay in the Type FT 11 Case Sub 19 57D7900 ...

Страница 23: ...nal Schematic of the Double Trip Circuit Closing Relay with Indicating Instantaneous Trip Unit Figure 21 Internal Schematic of the Double Trip Circuit Closing Relay with Indicating Instantaneous Trip Unit to Separate Terminals Sub 5 57D4526 Sub 3 184A061 ...

Страница 24: ...ABB Inc 4300 Coral Ridge Drive Coral Springs Florida 33065 Telephone 1 954 752 6700 Fax 1 954 345 5329 www abb com substation automation IL 41 101 Revision U ABB ...

Отзывы: