Chapter 7 Setpoint
The setpoint menu is normally accessed from the Base Display by a clicking on the encoder
knob.
If you wish to change the displayed value, click on the knob again and the change indicators
will start to flash to show that you are now in change mode. Twist the knob, clockwise to
increase the value, anti-clockwise to decrease.
When the desired value is shown, click on the knob to acknowledge. To return to the Base
display, twist the knob.
For configurations involving a single output signal the setpoint is the starting point for the
output signal.
For configurations involving two diverging output signals with neutral zone (heating –
cooling) the setpoint is placed in the middle of the neutral zone.
For configurations involving two outputs without neutral zone (heating – heating, cooling –
cooling, heating – damper or cooling – damper) the setpoint value is the starting point for the
first sequence (AO2)
Control mode 4, Radiator circuit control
If no room sensor is configured the setpoint menu is used to add a parallel displacement to
the outdoor curve. The displacement can be either positive or negative. The setpoint is shown
as
Δ
SP.
If room sensor is activated the Setpoint menu is used to set the room temperature instead of
adding a parallel displacement.
An optional room sensor can be connected to UI1. If a room sensor is used, it must be
connected to the Optigo before control mode 4 is selected. Otherwise, the controller will not
detect the sensor. To activate/deactivate the room sensor it has to be connected/not connected
to the Optigo before control mode 4 is selected. The control program is automatically
adapted when a room sensor is connected. Any room temperature offset will displace the
supply setpoint as to eliminate the offset. The room controller is a P-controller with a fixed
P-band of 3K. The setpoint is shown as SP
To indicate that room control is activated the display symbol showing a thermometer outside
the house is replaced by a thermometer inside the house.