Optigo OP10 user manual
Chapter 5
Control modes
19
Control mode 4, Radiator circuit control with outdoor curve
GT1
GT2
For this control mode you need two sensors, GT1 “Supply temperature” on AI1 and GT2
“Outdoor sensor” on AI2.
You can also have a room temperature sensor on UI1 to let the room temperature offset give
correction to the supply temperature. Wire UI1 as an analogue input.
3-Position control
Instead of the analogue output you can configure a 3-position (increase / decrease) output
using DO1 and DO2. DO1 is used for increase signal and DO2 for decrease. This option
cannot be combined with alarm output.
A single P control loop is used.
Control curve
The supply temperature setpoint is determined by a outdoor temperature/supply temperature
curve. The basic control curve is a straight line between the two setpoints SP
L
and SP
H
where
SP
L
is the supply temperature to be held when the outdoor temperature is +20°C and SP
H
is
the temperature to be held at an outdoor temperature of -20°C. An extra temperature boost
can be added at 0°C outdoor temperature. The boost receeds from the set value to 0 over ±3
degrees. In the Setpoint menu a parallel displacement of the whole curve can be added.
Supply temp
Outdoor temp
SP
H
SP
L
-20
0
+20
Room sensor
An optional room sensor can be connected to UI1. If a room sensor is used, it must be
connected to the Optigo before control mode 4 is selected. Otherwise, the controller will not
detect the sensor. To activate/deactivate the room sensor it has to be connected/not connected
to the Optigo before control mode 4 is selected. The control program is automatically
adapted when a room sensor is connected. Any room temperature offset will displace the
supply setpoint as to eliminate the offset. The room controller is a P-controller with a fixed
P-band of 3K.
If room sensor is activated the Setpoint menu is used to set the room temperature instead of
adding a parallel displacement.
To indicate that room control is activated the display symbol showing a thermometer outside
the house is replaced by a thermometer inside the house.