Optigo OP10 user manual
Chapter 5
Control modes
15
For control mode 2, “Supply air temperature control with outdoor compensation” you need
two sensors, “Supply air sensor” on AI1 and “Outdoor sensor” on AI2.
For control mode 3, “Cascade connected room / extract air temperature control” you also
need 2 sensors, “Supply air sensor” on AI1 and either “Room sensor” or “Extract sensor” on
AI2.
The analogue outputs can be configured to the following combinations:
AO1
/
AO2
1. Heating
/ -
2. Cooling
/
-
3. Heating
/ Cooling
4. Heating
/ Heating
5. Cooling
/ Cooling
6. Heating
/ Damper
7. Cooling
/ Damper
In alternative 4, Heating-Heating AO2 will be activated first on increasing heat demand.
In alternative 5, Cooling-Cooling AO2 will be activated first on increasing cooling cemand.
In alternative 6, Heating-Damper, at temperatures above the setpoint the damper on AO2 will
be fully open. On increasing heating demand, the damper on AO2 will first close to the set
minimum value before the heating output on AO1 starts to increase.
In alternative 7, Cooling-Damper, at temperatures below the setpoint the damper on AO2
will be fully open. On increasing cooling demand, the damper on AO2 will first close to the
set minimum value before the cooling output on AO1 starts to increase.